11
Voltage may still be present in AC side circuits after the indicator is off. Pay atten-
tion to the electricity safety during operating.
2.5
Circuit Diagram
The following figure shows the main circuit of the inverter.
figure 2-4
Circuit Diagram
•
DC switches can safely disconnect the PV input when necessary to ensure the safe op-
eration of the inverter and the safety of personnel.
•
The DC SPD provides a discharge circuit for the DC side over-voltage power to prevent
it from damaging the internal circuits of the inverter.
•
EMI filters can filter out the electromagnetic interference inside the inverter to ensure that
the inverter meets the requirements of electromagnetic compatibility standards.
•
The MPPT is utilized for DC input to ensure the maximum power from the PV array at dif-
ferent PV input conditions.
•
The inverter circuit converts the DC power into grid-compliant AC power and feeds it into
the grid.
•
The AC filter filters the output AC component of high frequency to ensure that the output
current meets the grid requirements.
•
The AC relay isolates the AC output of the inverter from the grid, making the inverter safe
from the grid in case of inverter failure or grid failure.
•
The AC SPD provides a discharge circuit for the AC side over-voltage power to prevent it
from damaging the internal circuits of the inverter.
2.6
Function Description
The inverter is equipped with the following functions:
Conversion Function
The inverter converts the DC into grid-compatible AC and feeds the AC into the grid.
Data Storage and Display
The inverter logs system information like running information, error records, etc.
User Manual