10 Operating the LCD Menu
User Manual
88
Main Screen
(Press
ENTER
)
→
Menu screen
(Press
×
3)
→
Set-param
(Press
ENTER
)
→
Enter password 111111
(Press
ENTER
)
→
Sys-param
(Press
ENTER
,
Press
×2)
→
Load default
(Press
ENTER
)
Press
ENTER
to confirm “load default”.
10.10.4 System Configuration
Main Screen
(Press
ENTER
)
→
Menu screen
(Press
×
3)
→
Set-param
(Press
ENTER
)
→
Enter password 111111
(Press
ENTER
)
→
Sys-param
(Press
ENTER
,
Press
×3)
→
Sys-config
(Press
ENTER
)
On the “Sys-config” screen,
scroll pages by
Pressing
ENTER
and
Press
to
select one item.
For each item setting,
Press
to move the cursor right
and
Press
to set the
appropriate value.
Confirm settings by
Pressing
ENTER
.
Item
Description
Buzzer
OFF
(reserved)
Low Power
OFF
(reserved)
Role
M
(master inverter) or
S
(slave inverter).
This is to set the communication role in power control. For the
cable connection and role definition, see “
Power Control
Settings
”.
Interface
RS485
or
ETH
(Ethernet), but not simultaneously.
The interface settings of master and slave inverters must be the
same.
This setting is enabled only when the
Role
is set to be
M
(master).
So, for slave inverters, you should reset the
Role
to be
S
(slave)
after interface setting.