User Manual
7 Commissioning
65
6.
(
Optional
) When the country code “AU” and the grid standard “Manual” are
selected,
Press
ENTER
to enter the “Pro-Stage” interface.
Press
/
to
choose the correct stage.
Press
to move cursor and
Press
to scroll up
time value. Confirm the settings by
Pressing
ENTER
. The following figure
shows the settings of single-stage protection parameters.
Countries
Country
:
[ AU ]
Grid Standard
AG
EE
EG
PN
PC
WP
Manual
Default
Pro-Stage
Single-stage
Multi-stage
Vgrid-min 210.0V
Vgrid-max 260.0V
Fgrid-min 47.00Hz
Fgrid-max 52.00Hz
7.
For other countries except “AU”, after
configuring the country code, there will be a
“Pro-Stage” type selection screen and then
corresponding sub-menu will come up. For
detailed information, please refer to “
10.12
Setting Protective Parameters
“.
Single-stage protection
: There is only one protection threshold range
for each grid voltage protection parameter.
Multi-stage protection
: The protection parameters for each grid
voltage protection can be set with two threshold ranges.
8.
According to the actual PV strings configuration
mode, choose the same mode in the inverter by
the LCD display menu (see “
10.14 Setting PV
Configuration Mode
”).