User Manual
10 Operating the LCD Menu
103
Confirm settings by pressing
ENTER
and enter the
“Setting confirmation” screen.
Check all above-mentioned parameter settings.
Confirm them by pressing
ENTER
. Cancel by pressing
ESC
and reset.
Multi-stage Protective Parameter
Select
“
Multi-stage
”
and
Press
to
enter into the submenus.
Press
to navigate the cursor;
Press
to enter into the editing mode,
then the selected parameter will be
shaded.
Press
to increase one-step value;
Press
to decrease one-step value.
Press
ENTER
to confirm the setting
and exit from the editing mode.
I-Max-V.time 060.00s
I-Max-V.grid 257.6V
Pro-param Multi
II-Max-V.time 000.10s
II-Max-V.grid 264.5V
Pro-param Multi
I-Min-V.time 000.20s
I-Min-V.grid 184.0V
II-Min-V.time 000.20s
II-Min-V.grid 184.0V
Pro-param Multi
I-Max-F.time 000.20s
I-Max-F.grid 51.50Hz
II-Max-F.time 000.20s
II-Max-F.grid 51.50Hz
Pro-param Multi
I-Min-F.time 000.20s
I-Min-F.grid 47.50Hz
II-Min-F.time 000.20s
II-Min-F.grid 47.50Hz
Tab. 10-13
Multi-stage Protective Parameters Explanation
Parameter
Explanation
Max-V. prote
Over-voltage protection
Ⅰ
-Max-V. grid
Stage
Ⅰ
Grid over-voltage (U>)
Ⅰ
-Max-V. time
Stage
Ⅰ
Grid over-voltage (U>) tripping time
Ⅱ
-Max-V. grid
Stage
Ⅱ
Grid over-voltage (U>>)
Ⅱ
-Max-V. time
Stage
Ⅱ
Grid over-voltage (U>>) tripping time
Min-V. prote
Under-voltage protection
Ⅰ
-Min-V. grid
Stage
Ⅰ
Grid under-voltage (U<)
Ⅰ
-Min -V. time
Stage
Ⅰ
Grid under-voltage (U<) tripping time
Ⅱ
-Min -V. grid
Stage
Ⅱ
Grid under–voltage (U<<)
Ⅱ
-Min -V. time
Stage
Ⅱ
Grid under–voltage (U<<) tripping time
Max-F. prote
Over-frequency protection
Ⅰ
-Max-F. grid
Stage
Ⅰ
Grid over-frequency (f>)
Ⅰ
-Max-F. time
Stage
Ⅰ
Grid over-frequency (f>) tripping time
Ⅱ
-Max-F. grid
Stage
Ⅱ
Grid over-frequency (f>>)
Ⅱ
-Max-F. time
Stage
Ⅱ
Grid over-frequency (f>>) tripping time
Min-F. prote
Under-frequency protection
Ⅰ
-Min-F. grid
Stage
Ⅰ
Grid under-frequency (f<)