Apply an IP address, subnet mask, default gateway and port number for the inverter
from your network administrator.
If there is more than one inverter and all the inverters are set to DHCP [OFF],
a unique IP address should be assigned to each inverter. The configuration
procedure should be performed only by qualified personnel.
10.14
Setting PV Configuration Mode
Main Screen
(Press
ENTER
)
→
Menu screen
(Press
×
3)
→
Set-param
(Press
ENTER
)
→
Enter password 111111
(Press
ENTER
, Press
×
4)
→
PV config mode
(Press
ENTER
)
On the “PV config mode” screen, Press
to choose
PV configuration mode, Press
ENTER
to confirm the
settings.
DO NOT change the PV configuration mode when the inverter is operating.
10.15
Special Settings for Austria and Vorarlberg
The differences focus on “Run-param” and “Pro-param” as shown below.
10.15.1
Over-frequency Setting for Austria and Vorarlberg
If the “Countries”
selection is “AT” (Austria)
or “VB(DE)” (Vorarlberg),
the “Derating Slope” *
and “Recover-Slope”*
will display in the
“Run-param” screen.
When the grid frequency is between 50.2 Hz and 51.5 Hz, inverter will decrease
power according to the “Derating Slope”.