10 Operating the LCD Menu
User Manual
108
Press
to select parameter,
Press
to move cursor
right and
Press
to set the appropriate value.
Confirm settings by
pressing
ENTER
.
Tab. 10-17
Italy Grid protection Recovery Value
Parameter
Explanation
Fmax
recover
Inverter can start operating only when the grid frequency is below
Fmax recovery.
The fault recovery value when the grid over-frequency occurs.
Fmin recover
Inverter can start operating only when the grid frequency is above
Fmin recovery.
The fault recovery value when the grid under-frequency occurs.
Vmax
recover
Inverter can start operating only when the grid voltage is below
Vmax recover.
The fault recovery value when the grid over-voltage occurs.
Vmin recover
Inverter can start operating only when the grid voltage is above Vmin
recover.
The fault recovery value when the grid under-voltage occurs.
Confirm settings by pressing
ENTER
and enter the
“Setting confirmation” screen.
Check all above-mentioned parameter settings. Confirm
them by pressing
ENTER
. Cancel by pressing
ESC
and
reset.
“IT” Multi-stage Protective Parameter
Select
“
Multi-stage
”
and
Press
to
enter into the submenus.
Press
to navigate the cursor;
Press
to enter into the editing mode, then
the selected parameter will be shaded.
Press
to increase one-step value;
Press
to decrease one-step value.
Press
ENTER
to confirm the setting
and exit from the editing mode.