10 Operating the LCD Menu
User Manual
90
10.11
Setting Running Parameter
10.11.1 Main Screen of Run-param
Main Screen
(Press
ENTER
)
→
Menu screen
(Press
×
3)
→
Set-param
(Press
ENTER
)
→
Enter password 111111
(Press
ENTER
, Press
)
→
Run-param
(Press
ENTER
)
On the “Run-param” screen,
scroll pages by pressing
ENTER
and press
to
select one item.
For each item setting,
Press
to move the cursor right
and
Press
to set the
appropriate value.
Confirm settings by
Pressing
ENTER
.
Tab. 10-4
Specification of Running Parameters
Parameter
Explanation
Default
Range
Standby
time
The time from
inverter initialization
to inverter feeding
power to grid.
Austria and
Vorarlberg:
30s
Others: 20s
20s…255s
Recover
time
The time from the
fault is cleared to
inverter feeding
power to grid.
Austria, Italy, and
Vorarlberg: 300s
Others: 30s
30s…900s
P-W limits
Inverter
active
power limits.
100.0% 0...100%
ISO-protect
Protection value of
the insulation
resistance.
200kohm 10kohm...1000kohm
PF Power
factor.
+1.000
-1.000…-0.800/+0.800
…+1.000
Q-Var limits
Inverter
reactive
power limits.
0.0% 0...+100%/0…-100%
Q-Var
switch Whether to start
inverter reactive
power adjustment
function.
[Pf] [Pf]/[Qt]/[Off]/[Q(P)]/[Q
(U)]