Threshold for leakage current protection
1.00~10.00 A
Zero-power mode
Enable/Disable
Active islanding
Enable/Disable
Threshold for grid voltage unbalance
protection
3.0~20.0 %
Delay for grid voltage unbalance protection
0.1~600.0 s
Manual start after fault
Enable/Disable
Insulation monitoring alarm threshold
15~1000 KΩ
Insulation monitoring protection threshold
15~100 KΩ
Delay for insulation monitoring measuring
30s, 60s, 150s, 180s
Insulation monitoring activation
Enable/Disable
Insulation monitoring switching interval
15min, 30min
DC undervoltage setpoint
SC1200UD-US:680.0-1550.0 V
SC1375UD-US: 780.0-1550.0 V
SC1575UD-US:895.0-1550.0 V
SC1725UD-US: 980.0-1550.0 V
DC overvoltage setpoint
SC1200UD-US:680.0-1550.0 V
SC1375UD-US: 780.0-1550.0 V
SC1575UD-US:895.0-1550.0 V
SC1725UD-US: 980.0-1550.0 V
Threshold for DC overcurrent protection
193~2288 A
Delay for DC overcurrent tripping
40~600000 ms
10-min overvoltage protection value
100.0~150.0 %
6.7.5 System Parameters
Step 1
Click [Device Monitoring] to enter the corresponding interface.
Step 2
Click the button [
] in the left device list bar, select the desired device type from the
drop-down list, and select corresponding device.
Step 3
Click [System Parameters] to view the system parameters of the device.
-- -- E
En
nd
d
For specific setting method, refer to
.
Operation Manual