14
3.2.3 Communication with BMS
PCS can communicate with battery management system (BMS) to monitor the state of
the battery and protect the battery according to the battery state. Communication
supports the CAN and RS485 methods.
F
Fiig
gu
urre
e 3
3--5
5 PCS communicates with BMS
3.3
Circuit Diagram
PCS realizes rectification and inversion through 3-phase full bridge conversion. The
rectified output feeds to the storage batteries through EMC filter. The inverted output
turns to sine-wave voltage through LC filter and then feeds to the grid after step-up by
3-phase transformer. The circuit diagram is shown in
Figure 3-6 PCS circuit diagram
.
F
Fiig
gu
urre
e 3
3--6
6 PCS circuit diagram
Operation Manual