29
Step 3
Click [Operation Parameters] to view the running parameters of the device.
-- -- E
En
nd
d
P
Pa
arra
am
me
ette
err
R
Ra
an
ng
ge
e
Timed Charge and Discharge
Enable/Disable
DC parallel mode
DC parallel, DC independent
On / Off / Standby
On, Off, Standby
Working mode
Off-grid mode, on-grid mode, or VSG
mode
Charge/Discharge Mode
Grid-connected constant current,
Grid-connected constant voltage,
Grid-connected constant power (AC),
Grid-connected constant power (DC)
Active power soft start
Enable/Disable
Active/Reactive priority
Reactive priority/Active priority
On-grid reactive power regulation mode
Closing/Power factor setting/
Reactive power ratio setting/Reactive
power operation Q(U) setting/
Reactive power operation Q(P)
setting
Black start beat
0~65535
Black start activation
Enable/Disable
Set on-grid power factor
-1.000~1.000
Set on-grid reactive power ratio
①
-100.0~100.0 %
On-grid constant power value (DC)
-100.0~100.0 %
On-grid constant power value (AC)
-100.0~100.0 %
On-grid constant current value
-1935~1935 A
On-grid constant voltage value
SC1200UD-US: 700.0~1500.0V
SC1375UD-US: 800.0~1500.0V
SC1575UD-US: 915.0~1500.0 V
SC1725UD-US: 1000.0~1500.0V
On-grid constant voltage current limit
0~1935 A
Primary frequency regulation control
Enable/Disable
Operation Manual