135
DC Power Source Requirements
The information in this section applies to the DC version of the Netra 440 server.
gives DC power source requirements for each power supply in the Netra
440 server, and
gives DC power source requirements for the Netra 440
server as a whole.
TABLE
C-4
DC Operating Power Limits and Ranges for Each Power Supply in the Netra
440 Server
Description
Limit or Range
Operating input voltage range
-40 VDC to -75 VDC
Maximum operating input current
11.5 A
Maximum operating input power
450 W
TABLE
C-5
DC Operating Power Limits and Ranges for the Netra 440 Server
Description
Limit or Range
Operating input voltage range
-40 VDC to -75 VDC
Maximum operating input current
23 A
Maximum operating input power
900 W