98
Netra 440 Server Service Manual
• August
2004
Installing the ALOM System Controller Card
Caution –
The system supplies power to the ALOM system controller card slot even
when the system is powered off. To avoid personal injury or damage to the ALOM
system controller card, you must disconnect the AC or DC power cables before
servicing the ALOM system controller card.
1. Locate the slot for the ALOM system controller card.
Note –
Ensure that you install the ALOM system controller card into the ALOM
slot. Though the ALOM system controller card might physically fit into a PCI slot, it
does not function if installed there.
Caution –
Follow the instructions in the next step carefully or you may damage the
ALOM system controller card or the motherboard.
2. Insert the ALOM system controller card into its slot on the motherboard
(
a. Insert the faceplate end of the card into the appropriate opening in the system
back panel.
b. Using both hands to apply even pressure along the edge of the card, push the
card into the connectors on the motherboard.