70
| Optidrive P2 User Guide |
Version 3.07
www.invertekdrives.com
Index
Sub index Function
Access
Type
PDO Map Default value
1A00h
0
TX PDO1 mapping / No. of entries
RW
Unsigned 8
N
4
1
TX PDO1 1st mapped object
RW
Unsigned 32
N
200A0010h
2
TX PDO1 2nd mapped object
RW
Unsigned 32
N
200B0010h
3
TX PDO1 3rd mapped object
RW
Unsigned 32
N
200D0010h
4
TX PDO1 4th mapped object
RW
Unsigned 32
N
200E0010h
1A01h
0
TX PDO2 mapping / No. of entries
RW
Unsigned 8
N
4
1
TX PDO2 1st mapped object
RW
Unsigned 32
N
200F0010h
2
TX PDO2 2nd mapped object
RW
Unsigned 32
N
20100010h
3
TX PDO2 3rd mapped object
RW
Unsigned 32
N
20110010h
4
TX PDO2 4th mapped object
RW
Unsigned 32
N
200C0010h
9.3.7. Manufacturer Specific Object Table
The following table shows some of the manufacturer specific object dictionary for Optidrive P2. For a complete list, refer to the
Optidrive P2 CAN Open Application Note.
Index
Sub index Function
Access
Type
PDO Map Remark
2000h
0
Control command register
RW
Unsigned 16
Y
See Note Below
2001h
0
Speed reference
RW
Integer 16
Y
500 = 50.0Hz
2002h
0
Torque reference
RW
Integer 16
Y
1000 = 100.0%
2003h
0
User ramp reference
RW
Unsigned 16
Y
500 = 5.00s
200Ah
0
Drive status register
RO
Unsigned 16
Y
See Note Below
200Bh
0
Motor speed Hz
RO
Unsigned 16
Y
500 = 50.0Hz
200Dh
0
Motor current
RO
Unsigned 16
Y
123 = 12.3A
200Eh
0
Motor torque
RO
Integer 16
Y
4096 = 100.0%
200Fh
0
Motor power
RO
Unsigned 16
Y
1234 = 12.34kW
2010h
0
Drive temperature
RO
Integer 16
Y
30 = 30°C
2011h
0
DC bus value
RO
Unsigned 16
Y
2012h
0
Digital input status
RO
Unsigned 16
Y
2013h
0
Analog input 1 (percentage)
RO
Unsigned 16
Y
2014h
0
Analog input 2 (percentage)
RO
Unsigned 16
Y
2015h
0
Analog output 1
RO
Unsigned 16
Y
2016h
0
Analog output 2
RO
Unsigned 16
Y
2017h
0
relay output 1
RO
Unsigned 16
Y
2018h
0
relay output 2
RO
Unsigned 16
Y
2019h
0
relay output 3 (extension card)
RO
Unsigned 16
Y
201Ah
0
relay output 4 (extension card)
RO
Unsigned 16
Y
201Bh
0
relay output 5 (extension card)
RO
Unsigned 16
Y
203Ah
0
Kilowatt hours (Can be reset by user)
RO
Unsigned 16
Y
203Bh
0
Megawatt hours (Can be reset by user)
RO
Unsigned 16
Y
203Ch
0
KWh meter
RO
Unsigned 16
Y
203Dh
0
MWh meter
RO
Unsigned 16
Y
203Eh
0
Total run hours
RO
Unsigned 16
Y
203Fh
0
Total run minute/second
RO
Unsigned 16
Y
2040h
0
Current run hours (Since last enable)
RO
Unsigned 16
Y
2041h
0
Current run minute/second
RO
Unsigned 16
Y
2042h
0
Time to next service
RO
Unsigned 16
Y
2043h
0
Room Temperature
RO
Unsigned 16
Y
2044h
0
Speed controller reference
RO
Unsigned 16
Y
2045h
0
Torque controller reference
RO
Unsigned 16
Y
2046h
0
Digital pot speed reference
RO
Unsigned 16
Y
9
Serial Communications