SRC Service Manual
Revision 02
Aug 2007
7.4 Factory Parameter List
Factory parameters are locked and can only be modified by entering a special
code reserved for authorized factory trained technicians. Altering these
parameters may significantly effect dryer operation and could allow operating
conditions which are unsafe or damaging to personnel and/or equipment.
Altering the values of these parameters by anyone other than a trained
authorized factory technician, or without the express written authorization of the
factory, will void warranty. Contact Sullair for further information.
!
Parameter
Description
Units
Min
Max
Default
A7
High Dewpoint Warning Delay at Startup
min
0
60
15
A8
Low Dewpoint Alarm Setting
o
C
-9.9
10
0
B4
Reset Working Hours
-
0 (no)
1 (yes)
0 (no)
B5
Coolant Tank Temperature
o
C/
o
F
-
-
-
B6
Disable Access to Factory Parameters
-
0 (no)
1 (yes)
0 (no)
B7
Reset Alarm Report
-
0 (no)
1 (yes)
0 (no)
C1
Coolant Temperature Setting
o
C -9.9 70 1
C2
Coolant Temperature Differential
o
C
0
30
1
C3
Compressor OFF Time Delay
sec
0
600
1
C4
Immediate Compressor OFF Temp
o
C
-9.9
15
0.5
C5 Software
Identifier
-
d.t.1
d.t.1
d.t.1
C6
Compressor ON Time Delay
sec
0
900
60
D4
Drain Open Delay
sec
0
900
60
D5
Drain Close Delay (Normal Cycle)
sec
0
120
5
D6
Drain Close Delay (Extended Cycle)
sec
0
300
10
D7
Extended Cycle Interval*
-
0
900
100
D8 Drain
Alarm
Setting*
sec
10
900
30
For further information on how the “C” parameters affect cycling operation, refer to Section 8.
For further information on how the “D” parameters affect drain functioning, refer to Section 9.