SRC Service Manual
Revision 02
Aug 2007
7.3 Accessing & Modifying User Parameters
To access the User Parameters:
•
Press
the
Alarm Reset & Alarm Report
buttons
simultaneously.
&
The display will show you are at Parameter “A1”.
To view and modify the User Parameters:
or
•
Press
the
Up
or
Down
buttons to scroll through the parameters.
or
•
When you get to the parameter you want, press
Enter
to see it’s value.
•
Press
the
Up
or
Down
buttons to modify it’s value*.
or
•
Press
Enter
to save your changes.
•
Press Exit to leave the parameter.
* Parameters B3 & B8 are passcode protected and cannot be changed or reset without the proper code. Contact Sullair for further
information.
Note that once inside the parameters menu, the meaning of the buttons is different from the
standard operation. (See section 3.2) It is not possible to:
•
Turn the dryer On or Off
•
Reset a warning or alarm
•
Display the alarm report
•
Activate the drain valve
Once in the parameters menu, if the user does not press any button for 5 minutes, the
controller will exit the menu and return to standard operating mode.
To exit the parameter menu and return to the standard operating mode, press Exit.
When in standard operating model the display will show either:
•
“OFF” when the dryer is OFF,
•
“r.OF” with dryer is in Remote OFF mode,
•
the dew-point temperature when the dryer is ON and has no alarm, or
•
the alarm or warning code if the dryer is ON and has an alarm or warning.
Page 31 of 56