Section 4
INSTALLATION
17
4.1 MOUNTING OF COMPRESSOR
A foundation or mounting capable of supporting
the weight of the compressor, and rigid enough to
maintain the compressor frame level and the com-
pressor in alignment is required. The compressor
frame must be leveled and secured with foundation
bolts, and full uniform contact must be maintained
between the frame and foundation. No piping
loads shall be transmitted to the compressor at the
external connections.
4.2 VENTILATION AND COOLING
For air---cooled compressors, select a location to
permit sufficient unobstructed air flowing in and out
to the compressor to keep the operating tempera-
ture stable. The minimum distance that the com-
pressor should be from surrounding walls is three
(3) feet (1m). To prevent excessive ambient tem-
perature rise, it is imperative to provide adequate
ventilation.
For water---cooled compressors, it is necessary to
check the cooling water supply. The water system
must be capable of supplying the flows shown in
Table I---Water Supply Requirements (Water---
cooled), and must be maintained at all times.
These figures apply to a compressor running at full
load with an aftercooler. For cooler water or a par-
tially loaded compressor, slightly less water is re-
quired. However, for hotter water the flow require-
ments are significantly greater.
Table 2---Ventilation Requirements indicates the
ventilation requirements necessary to keep the
compressor running at a normal operating temper-
ature. The fan air requirement is the volume of air
which must flow through the compressor for proper
ventilation. The specified heat rejection require-
ment is the amount of heat that is radiated by the
compressor. This heat must be removed to assure
a normal operating temperature. With air---cooled
compressors it is possible to use this heat for space
heating, providing no additional pressure drop is
created across the fan. Consult a Sullair office for
assistance in utilizing this heat.
DO NOT
install a water---cooled or an air---cooled/
aftercooled compressor where it will be exposed to
temperatures less than 32
_
F(0
_
C).
4.3 SERVICE AIR PIPING
Service air piping should be installed as shown in
Figure 4---1. A shut---off valve should be installed to
isolate the compressor from the service line if re-
quired. Also notice that the service line should be
equipped with water legs and condensate drains
throughout the system.
WARNING
!
“The Plastic Pipe Institute recommends against the
use of thermoplastic pipe to transport compressed
air or other compressed gases in exposed above
ground locations, e.g. in exposed plant piping.” (
I
)
Sullube 32 should not be used with PVC piping sys-
tems. It may affect the bond at cemented joints. Cer-
tain other plastic materials may also be affected.
(
I
) Plastic Pipe Institute, Recommendation B,
Adopted January 19, 1972.
(I)
Water pressure should be between 25 and 75 psig (1.7 and 5.2 bar).
TABLE 1--WATER SUPPLY REQUIREMENTS (WATER--COOLED)
WATER FLOW
(I)
WATER TEMP.
GMP (LITERS)
0
˚
F (
˚
C)
25HP (18KW)
30HP (22KW)
40HP (30KW)
70 (21)
3.75 (14.2)
4.50 (17.0)
5.75 (21.8)
80 (26.6)
5.00 (18.9)
6.00 (22.7)
7.50 (28.4)
Cooling Type
Air---cooled with Aftercooler
Water---cooled
Motor HP/KW
25/18
30/22
40/30
25/18
30/22
30/40
Fan Air CFM
2500/4250
2500/4250
3500/5950
720/1220
720/1220
720/1220
M
3
/Hr
(II)
Ventilating Air/
Heat Rejection
BTU/Hour
76980/
88800/
118320/
8500/
10000/
13000
KCal/Hour
19500
22500
29900
2150
2550
3300
Cooling Water/
Heat Rejection
BTU/Hour
Kcal/Hour
(II)
Applies to compressor with canopy only (vent fan).
(I)
Values based on: 100% RH, 85
˚
F Ambient
TABLE 2--VENTILATION REQUIREMENTS
(I)
Содержание LS-10 18KW 24KT
Страница 6: ...NOTES...
Страница 15: ...Section 2 DESCRIPTION 9 Figure 2 3 Control System...
Страница 18: ...12 NOTES...
Страница 22: ...16 NOTES...
Страница 26: ...20 NOTES...
Страница 34: ...28 NOTES...
Страница 37: ...Section 6 SUPERVISOR II 31 MESSAGE DISPLAY SYSTEM GRAPHIC DISPLAY KEYPADS Figure 6 1 Supervisor II Panel...
Страница 38: ...32 NOTES...
Страница 48: ...Section 7 MAINTENANCE 42 Figure 7 7 Piping and Instrumentation Diagram Standard...
Страница 49: ...Section 7 MAINTENANCE 43 Figure 7 8 Piping and Instrumentation Diagram Supervisor II...
Страница 50: ...44 NOTES...
Страница 52: ...Section 8 ILLUSTRATIONS AND PARTS LIST 46 8 3 MOTOR COMPRESSOR FRAME AND PARTS...
Страница 54: ...Section 8 ILLUSTRATIONS AND PARTS LIST 48 8 3 MOTOR COMPRESSOR FRAME AND PARTS...
Страница 56: ...Section 8 ILLUSTRATIONS AND PARTS LIST 50 8 4 COOLER ASSEMBLY...
Страница 58: ...Section 8 ILLUSTRATIONS AND PARTS LIST 52 8 5 AIR INLET SYSTEM...
Страница 60: ...Section 8 ILLUSTRATIONS AND PARTS LIST 54 8 6 COOLING AND LUBRICATION SYSTEM...
Страница 62: ...Section 8 ILLUSTRATIONS AND PARTS LIST 56 8 6 COOLING AND LUBRICATION SYSTEM...
Страница 68: ...Section 8 ILLUSTRATIONS AND PARTS LIST 62 8 8 CONTROL SYSTEM AND ELECTRICAL PARTS...
Страница 70: ...Section 8 ILLUSTRATIONS AND PARTS LIST 64 8 8 CONTROL SYSTEM AND ELECTRICAL PARTS...
Страница 72: ...Section 8 ILLUSTRATIONS AND PARTS LIST 66 8 9 INSTRUMENT PANEL...
Страница 76: ...Section 8 ILLUSTRATIONS AND PARTS LIST 70 8 11 DECAL GROUP 1 2 3 4 5 6 7 8 9 10 11...
Страница 78: ...Section 8 ILLUSTRATIONS AND PARTS LIST 72 8 11 DECAL GROUP 12 13 14 15 16 17 18 19 20...
Страница 80: ...Section 8 ILLUSTRATIONS AND PARTS LIST 74 8 11 DECAL GROUP 21 22 23 24 25 26 27...
Страница 82: ...Section 8 ILLUSTRATIONS AND PARTS LIST 76 8 11 DECAL GROUP ADD FULL 29 28 30 31...
Страница 84: ...Section 8 ILLUSTRATIONS AND PARTS LIST 78 8 12 WIRING DIAGRAM ELECTRO MECHANICAL AIR COOLED WATER COOLED...
Страница 85: ...Section 8 ILLUSTRATIONS AND PARTS LIST 79 8 13 WIRING DIAGRAM SUPERVISOR II DELUXE AIR COOLED WATER COOLED...
Страница 88: ...NOTES...
Страница 89: ...NOTES...