Section 5
OPERATION
25
AUTOMATIC OPERATION MODE
In this mode the compressor will start if line pres-
sure (P2) is less than the
LOAD
parameter. It will
stop if the compressor runs unloaded for the num-
ber of minutes indicated by the
UNLD TIM
parame-
ter. To put the compressor in automatic mode press
“ ”. If P2 is already less than
LOAD
the compres-
sor will start immediately, otherwise the system sta-
tus will indicate
STANDBY
and the LED marked
AUTO
will flash.
If the compressor is already running, but in continu-
ous mode, pressing “ ” will switch operation to
automatic. Pressing “ ” while already running in
automatic mode will cause the Supervisor to turn
off the common fault relay, if engaged, and clear
any maintenance indicators.
In automatic mode the compressor can be
stopped manually by pressing “
O
”
.
Stopping the
compressor using “
O
” will put the Supervisor in
manual stop mode.
Regardless of whether in “automatic” or “manual”
mode, control of the load solenoid will be based on
the parameters
UNLD
and
LOAD.
This operation is
as follows:
P2 > UNLD -- --> load solenoid turned off
P2 < LOAD -- --> load solenoid turned on
POWER FAILURE RESTART
If the restart timer (RST TIME parameter) is dis-
abled the compressor will not try to start after a
power up. If this time is set to a value, the machine
will go into standby after power up. When the line
pressure drops below the load setpoint, the restart
timer will start timing. When the timer expires the
machine will start.
SEQUENCING MODES
The following is a brief description of sequencing
modes. For details see the Supervisor
II
Sequenc-
ing & Protocol Manual (See Recommended Spare
Parts List)
.
S
DISABLED
--- Responds to status and
parameter change messages via the
RS485 network but will not respond to
start, stop, load or unload messages.
S
REMOTE
--- Responds to status and pa-
rameter change messages but will not re-
spond to start, stop, load or unload mes-
sages. The remote inputs and outputs are
enabled (start/stop, load/unload, master/
local).
S
SLAVE
--- Will respond to all messages,
but will not start or load unless command-
ed to do so by a message. This mode is
used to control the machine from a master
computer.
S
HOURS
--- Sends status message about
once a second; starts, loads and unloads
machines based on sequencing hours.
S
COM ID #
--- Sends status message
about once a second; starts, loads and un-
loads machines based on machine COM
ID#.
5.9 PURPOSE OF CONTROLS -- SUPERVISOR
II
CONTROL OR INDICATOR
PURPOSE
EMERGENCY STOP SWITCH
Pushing in this switch, found adjacent to the Supervi-
sor, cuts all AC outputs from the latter and de---ener-
gizes the starter. A fault message (E STOP) is dis-
played by the Supervisor until the button is pulled out
and the “
O
” pad is depressed.
DISCHARGE TEMPERATURE PROBE---T1
Shuts the compressor down when the compressor
discharge temperature exceeds 240
_
F (116
_
C). Con-
tinually monitors air/fluid mixture discharged from the
compressor unit.
AIR END DISCHARGE PRESSURE---P1
Shuts the compressor down when the compressor dis-
charge pressure exceeds P1 MAX. Continually moni-
tors the discharge pressure of the compressor unit. In-
dicates pressure in compressor sump upon start---up to
verify rotor motor rotation.
PACKAGE OUTLET PRESSURE---P2
Continually monitors service line pressure. When line
(Service Line Pressure)
pressure reaches the UNLOAD setting, the Supervisor
control signals the solenoid valve to unload the com-
pressor.
Содержание LS-10 18KW 24KT
Страница 6: ...NOTES...
Страница 15: ...Section 2 DESCRIPTION 9 Figure 2 3 Control System...
Страница 18: ...12 NOTES...
Страница 22: ...16 NOTES...
Страница 26: ...20 NOTES...
Страница 34: ...28 NOTES...
Страница 37: ...Section 6 SUPERVISOR II 31 MESSAGE DISPLAY SYSTEM GRAPHIC DISPLAY KEYPADS Figure 6 1 Supervisor II Panel...
Страница 38: ...32 NOTES...
Страница 48: ...Section 7 MAINTENANCE 42 Figure 7 7 Piping and Instrumentation Diagram Standard...
Страница 49: ...Section 7 MAINTENANCE 43 Figure 7 8 Piping and Instrumentation Diagram Supervisor II...
Страница 50: ...44 NOTES...
Страница 52: ...Section 8 ILLUSTRATIONS AND PARTS LIST 46 8 3 MOTOR COMPRESSOR FRAME AND PARTS...
Страница 54: ...Section 8 ILLUSTRATIONS AND PARTS LIST 48 8 3 MOTOR COMPRESSOR FRAME AND PARTS...
Страница 56: ...Section 8 ILLUSTRATIONS AND PARTS LIST 50 8 4 COOLER ASSEMBLY...
Страница 58: ...Section 8 ILLUSTRATIONS AND PARTS LIST 52 8 5 AIR INLET SYSTEM...
Страница 60: ...Section 8 ILLUSTRATIONS AND PARTS LIST 54 8 6 COOLING AND LUBRICATION SYSTEM...
Страница 62: ...Section 8 ILLUSTRATIONS AND PARTS LIST 56 8 6 COOLING AND LUBRICATION SYSTEM...
Страница 68: ...Section 8 ILLUSTRATIONS AND PARTS LIST 62 8 8 CONTROL SYSTEM AND ELECTRICAL PARTS...
Страница 70: ...Section 8 ILLUSTRATIONS AND PARTS LIST 64 8 8 CONTROL SYSTEM AND ELECTRICAL PARTS...
Страница 72: ...Section 8 ILLUSTRATIONS AND PARTS LIST 66 8 9 INSTRUMENT PANEL...
Страница 76: ...Section 8 ILLUSTRATIONS AND PARTS LIST 70 8 11 DECAL GROUP 1 2 3 4 5 6 7 8 9 10 11...
Страница 78: ...Section 8 ILLUSTRATIONS AND PARTS LIST 72 8 11 DECAL GROUP 12 13 14 15 16 17 18 19 20...
Страница 80: ...Section 8 ILLUSTRATIONS AND PARTS LIST 74 8 11 DECAL GROUP 21 22 23 24 25 26 27...
Страница 82: ...Section 8 ILLUSTRATIONS AND PARTS LIST 76 8 11 DECAL GROUP ADD FULL 29 28 30 31...
Страница 84: ...Section 8 ILLUSTRATIONS AND PARTS LIST 78 8 12 WIRING DIAGRAM ELECTRO MECHANICAL AIR COOLED WATER COOLED...
Страница 85: ...Section 8 ILLUSTRATIONS AND PARTS LIST 79 8 13 WIRING DIAGRAM SUPERVISOR II DELUXE AIR COOLED WATER COOLED...
Страница 88: ...NOTES...
Страница 89: ...NOTES...