Stulz DRH-04 Скачать руководство пользователя страница 9

(April, 2013)

DRH Series GEN1 Ultrasonic Humidifi er Installation, Operation & Maintenance Manual

1.6.12  Solid State Relay

The 48 VDC operating voltage for the Ultrasonic 

Nebulizer Units is switched on and off by a solid state 
DC relay controlled by the Level Controller.

1.6.13 Level Controller

The Level Controller is a microprocessor based 
device located in the electric box that receives inputs 
from sensors and other inputs and in turn controls the 
valves, fan and Ultrasonic Nebulizer Units. It consists 
of a DC-DC power supply to convert the 48VDC 
to 24VDC for the fans and solenoids and a further 
reduction to 5VDC for the microprocessor, sensors, 
power switches and either a Modbus interface to 
communicate with the Ultra-Series Controller or 
a simple standalone input interface depending on 
which model humidifi er was purchased. The 48 
VDC must be present at all times to allow the Level 
Controller microprocessor to monitor the inputs and 
control the outputs.

The microprocessor monitors the on/off command 
from either the Modbus or the input dry contact 
(depending on which model was purchased). If 
commanded on, the microprocessor checks the Low 
Water Float Switch and the High Water Float Switch. 
If the water is too low, the microprocessor turns on 
the Water Fill Valve Solenoid and monitors the Float 
Switches. When the water level is above the low 
water level, the fan is turned on. When the water 
level is above the high water level, the Water Fill 
Valve Solenoid is turned off and the Solid State Relay 
is turned on. When the water level falls below the 
high water level, the microprocessor turns the Water 
Fill Valve Solenoid on again to maintain optimal 
water level. When the on/off command is removed, 
the Solid State Relay is turned off and, after a few 
seconds time delay to eliminate the remaining mist 
from the humidifi er, the Fan is turned off.

Proportional control is accomplished by the 
microprocessor monitoring the proportional signal 
from the Modbus or proportional input (depending on 
which model was purchased). When the proportional 
signal is greater than 10% of the maximum input, the 
microprocessor will turn the Solid State Relay on and 
off in a pulse-width modulation control. The period 
of the pulse width is 1 second. For 10% control, the 
Solid State Relay is turned on for 0.1 second and off 
for 0.9 second. The on time increases as the input 
approaches 100%. At 100%, the Solid State Relay is 
on continuously.

Safety control is built into the microprocessor. The 
voltage applied to the transducer affects the amount 
of mist produced. Too high a voltage can cause 
damage to the transducer and too low a voltage 
prevents mist from being formed. The microprocessor 
monitors the 48 VDC to be within a range of voltages. 
If the voltage is out of range, the microprocessor will 
not energize the Solid State Relay.

If the temperature of the tank rises too high, the 
microprocessor turns off the Solid State Relay. 
If the temperature approaches freezing, the 
microprocessor turns off the Solid State Relay and 
the fan, and then drains the tank to prevent damage 
from freezing water. When the temperature returns to 
a safe level, normal operation is resumed.

A low level alarm is annunciated when the 
microprocessor sees the Low Level Float Switch 
indicate low water after the tank has been fi lled. A 
fi ll alarm is annunciated when the High Water Float 
Switch does not indicate the water level has been 
achieved after a predetermined amount of time. A 
transducer alarm is annunciated if the transducers 
have been energized and no water is used in a 
predetermined time (indicating no transducer is 
functioning). For the Modbus version of the Level 
Controller, failure to receive commands on the 
Modbus within a predetermined amount of time will 
annunciate a communications alarm.

The Level Controller has an LED that displays, via 
blinking, any alarm condition that occurred after 
power up. Each alarm is associated with a number of 
blinks, followed by a pause, and then the next alarm 
is displayed. To view the LED, the Mist Guide Cover 
must be removed and the electrical access cover 
removed. The LED blink pattern for each alarm is:

Number 
of Blinks

Alarm Condition

1

Low Voltage

2

High Voltage

3

Freeze

4

High Temperature

5

Low Water

6

Fill Alarm

7

Communications

8

Transducer

1-6

Содержание DRH-04

Страница 1: ...April 2013 DRH Series GEN1 Ultrasonic Humidifier Installation Operation Maintenance Manual MODELS DRH 04 DRH 08 DRH 06 DRH 16 READ AND SAVE THESE INSTRUCTIONS LIRE ET CONSERVER CES INSTRUCTIONS...

Страница 2: ...ntains confidential and proprietary information of Stulz Air Technology Systems Inc Distributing or photocopying this document for external distribution is in direct violation of U S copyright laws an...

Страница 3: ...1 3 3 Procedure For Operation 3 1 3 4 Precautions 3 2 3 5 Steps for Long Term Shutdown 3 2 4 0 Maintenance Repairs 4 1 4 1 Periodic General Maintenance 4 1 4 1 1 General 4 1 4 2 Maintenance Items and...

Страница 4: ...mation A bold text NOTE marks a short message in the information to alert you to an important detail A bold text CAUTION safety alert appears with infor mation that is important for protecting your eq...

Страница 5: ...g of the air inlet The humidifier may be filled with the condensed mist and electrical shorts may result CAUTION Observe the unit for water leakage A short circuit could occur if the humidifier is spl...

Страница 6: ...original warranty period or for 90 days from the date of installation whichever is greater Stulz Air Technology Systems Inc s warranty does not cover failures caused by improper installation abuse mis...

Страница 7: ...r supply temperature 40 F to 104 F Parts to be provided by user DI or RO supply water Water supply valve Water supply tubing 1 4 stainless steel or poly tubing rated for DI water power supply wiring a...

Страница 8: ...he water level is near an unsafe level and is closed when the water level is at a minimal level 1 6 5 Fan The 24VDC fan or fans both lightly pressurizes the air above the water to provide a path for t...

Страница 9: ...proportional signal is greater than 10 of the maximum input the microprocessor will turn the Solid State Relay on and off in a pulse width modulation control The period of the pulse width is 1 second...

Страница 10: ...l Avoid dropping or jarring the unit to prevent damage to the internal parts The unit should always be stored in a dry location prior to installation A Data Package has been sent with your unit It con...

Страница 11: ...ht of the unit Weight estimates can be found on the installation drawing provided with your unit Secure the unit with fasteners field supplied by others so that it will not move during operation Ensur...

Страница 12: ...side of the humidifier until some resistance is felt Then using an open end wrench on the reducer fitting screw the assembly 1 full turn to fully tighten it DO NOT tighten the filter strainer by gras...

Страница 13: ...correct electrical wire sizing from the control panel to the humidifiers for three different distances All wire sizes listed are for stranded THHN or NTW wire only Do not use solid conductor wire For...

Страница 14: ...Operation 1 Turn the main power source switch on the control box to the On position 2 Open the water supply valve allowing water to flow to the humidifier 3 Perform a manual drain cycle to flush any...

Страница 15: ...teps for Long Term Shutdown If the humidifier is not signalled to turn On for a period of three days the level control board will automatically signal the humidifier to operate a drain cycle When oper...

Страница 16: ...ch to Off and close the water supply valve WARNING Turn off power to the unit unless you are performing tests that require power With power and controls energized the unit could begin operating automa...

Страница 17: ...Cycle Description Necessary Tools Phillips screwdriver Air filter cleaning About once a week depending on the extent of contamination The interval should be short ened if environmental condi tions are...

Страница 18: ...ontrol box disconnect switch to Off and close the water supply valve 2 Loosen the bowl on the filter strainer assembly and remove it Photo 3 3 Remove the element and rinse the filter and the inside of...

Страница 19: ...cement 4 2 4 Float Switches 1 Loosen and remove the float panel mounting screws 2 Pcs Photo 8 Note Don t let the screws drop into the tank 2 Lift the float panel out and turn it over Photo 9 3 Check f...

Страница 20: ...the air flow guide Photo 13 4 Check the water tank interior for contamination Wipe and clean the water tank interior and clean the surface of the transducers etc in the water tank by wiping with a sof...

Страница 21: ...through the above checking remove the mist guide cover and air flow guide and check the interior of the water tank 4 3 Troubleshooting and Repair Should any failure occur make the necessary repairs re...

Страница 22: ...ply system overflowing Water supply solenoid valve is faulty Overflowing occurs even after power is turned off 4 Consumable parts Fan lead wires are loose or disconnected from the terminals Clean the...

Страница 23: ...ing the parts Photo 19 6 The transducers are visible when you rotate the tank to view the bottom Photo 20 7 The nebulizer print plates are on the side of the tank adjacent to the transducers Photo 21...

Страница 24: ...re ties bundling the sensor cable and unscrew the sensor wires from the terminal connectors on the printed circuit board 3 Connect the new sensor wires to the printed circuit board 4 Install the new s...

Страница 25: ...e the nuts to mount the new part Photo 27 5 Clean the spacer o ring groove and o ring 6 Assemble the new transducer with the spacer and o ring and install them with the saved mounting screws Photo 28...

Страница 26: ...laced it is recommended that the transducer be replaced also 6 Referring to Sect 4 4 2 Re assembling re assemble the unit by reversing the procedure described in Section 4 4 1 4 4 6 Water Solenoid Val...

Страница 27: ...rd remove the lead wire terminal connectors 3 Pcs from the board see Photos 6 7 Note Grasp the connectors when removing Never pull the lead wires 10 Slide the level control board out along the guides...

Страница 28: ...n UPS ground the customer is responsible for the shipping charges If you do not have established credit with STULZ you must give a freight carrier account number A written or faxed purchase order is r...

Страница 29: ...DRAWINGS 6 1 Layout Drawing of Humidifier Covers Removed to Show Parts 1 4 2 8 7 6 5 3 The bubble numbers in the drawing coincide with the item numbers listed below 1 Drain Stub 1 8 NPT 2 Water Supply...

Страница 30: ...L NC NO C L M DC DC SolidState Relay 4 3 X 1 X2 PCB Level Controller X1 2 X1 3 X1 5 X2 1 X2 2 X2 3 X2 4 X2 5 X2 6 X2 7 X2 8 X3 1 X3 2 X3 3 X3 4 X3 5 X3 6 X1 6 X1 7 X1 4 X1 8 From Control Box Nebulize...

Страница 31: ...lve Solenoid DrainValve Solenoid Fan HighLevel Switch LowLevel Switch OverTemp Sensor BLUE RED X1 1 X X 2 1 X 1 X 2 Current ofRelay 5A 10 12A 1 2 2 1 PinNumber 4 X1 2 X1 3 X1 1 X1 4 X1 2 X1 3 X1 Conne...

Страница 32: ...2013 DRH Series GEN1 Ultrasonic Humidifier Installation Operation Maintenance Manual OUD0077D April 2013 DRH Series GEN1 Installation Operation Maintenance Specifictions are subject to change without...

Отзывы: