Stulz DRH-04 Скачать руководство пользователя страница 24

(April, 2013)

DRH Series GEN1 Ultrasonic Humidifi er Installation, Operation & Maintenance Manual

4-9

4.4.3   Replacing the Temperature Sensor

The temperature sensor is mounted to either the fi rst nebulizer print plate or on the front of the water tank 
depending on when your unit was shipped. Referring to Section 4.4.1, “Preparation for Repairs” steps 1 - 5, 
place the water tank on a well lit work surface. Determine the sensor location (see photos 22 and 24). Refer 
to section 4.4.3.1 if the sensor is mounted on the nebulizer print plate. Refer to section 4.4.3.2 if the sensor is 
mounted on the tank.

25

Terminal 
Connector 

Nylon 
Screw 

Sensor 

Mica 
Pad 

Slots 

23

Nut 

Washer 

Shoulder Washer 

Sensor 

Mica Pad 

4.4.3.1 

Temperature Sensor on Nebulizer Print Plate

 

1) The temperature sensor is mounted to the fi rst nebulizer 
print plate. Using a 5.5 mm nut driver, remove the mounting 
nut holding the sensor in place. Remove the sensor and the 
insulating parts. Save the nut and insulating parts to mount the 
new sensor. 

 

 

  

       

          Photo 22

2) Carefully cut the wire ties bundling the sensor cable and 
unscrew the sensor wires from the terminal connectors on the 
printed circuit board.  

3) Connect the new sensor wires to the printed circuit board.

4) Install the new sensor to the print plate together with the 
saved mica pad and insulating parts. Ensure the insulating 
bushing is correctly placed to prevent the sensor from shorting 
to the mounting stud.   

 

 

          Photo 23

5) Referring to Sect. 4.4.2, “Re-assembling”, re-assemble the 
unit by reversing the procedure described in Section 4.4.1.

4.4.3.2 

Temperature Sensor on Water Tank

 

1) The temperature sensor is mounted on the front of the tank 
near the fl oat switches. Carefully cut the wire tie holding the 
sensor cable and remove the nylon screw holding the sensor 
in place. Remove the sensor and save the mica pad and nylon 
screw to mount the new sensor. 

                      Photo 24

2) Remove the terminal connector from the sensor and connect 
it to the new sensor. Ensure the three slots in the terminal 
connector are oriented upwards. 

 

          Photo 25  

3) Install the new sensor to the tank together with the saved 
mica pad. Cable tie the sensor cable restrain it. 

4) Referring to Sect. 4.4.2, “Re-assembling”, re-assemble the 
unit by reversing the procedure described in Section 4.4.1.

22

24

Содержание DRH-04

Страница 1: ...April 2013 DRH Series GEN1 Ultrasonic Humidifier Installation Operation Maintenance Manual MODELS DRH 04 DRH 08 DRH 06 DRH 16 READ AND SAVE THESE INSTRUCTIONS LIRE ET CONSERVER CES INSTRUCTIONS...

Страница 2: ...ntains confidential and proprietary information of Stulz Air Technology Systems Inc Distributing or photocopying this document for external distribution is in direct violation of U S copyright laws an...

Страница 3: ...1 3 3 Procedure For Operation 3 1 3 4 Precautions 3 2 3 5 Steps for Long Term Shutdown 3 2 4 0 Maintenance Repairs 4 1 4 1 Periodic General Maintenance 4 1 4 1 1 General 4 1 4 2 Maintenance Items and...

Страница 4: ...mation A bold text NOTE marks a short message in the information to alert you to an important detail A bold text CAUTION safety alert appears with infor mation that is important for protecting your eq...

Страница 5: ...g of the air inlet The humidifier may be filled with the condensed mist and electrical shorts may result CAUTION Observe the unit for water leakage A short circuit could occur if the humidifier is spl...

Страница 6: ...original warranty period or for 90 days from the date of installation whichever is greater Stulz Air Technology Systems Inc s warranty does not cover failures caused by improper installation abuse mis...

Страница 7: ...r supply temperature 40 F to 104 F Parts to be provided by user DI or RO supply water Water supply valve Water supply tubing 1 4 stainless steel or poly tubing rated for DI water power supply wiring a...

Страница 8: ...he water level is near an unsafe level and is closed when the water level is at a minimal level 1 6 5 Fan The 24VDC fan or fans both lightly pressurizes the air above the water to provide a path for t...

Страница 9: ...proportional signal is greater than 10 of the maximum input the microprocessor will turn the Solid State Relay on and off in a pulse width modulation control The period of the pulse width is 1 second...

Страница 10: ...l Avoid dropping or jarring the unit to prevent damage to the internal parts The unit should always be stored in a dry location prior to installation A Data Package has been sent with your unit It con...

Страница 11: ...ht of the unit Weight estimates can be found on the installation drawing provided with your unit Secure the unit with fasteners field supplied by others so that it will not move during operation Ensur...

Страница 12: ...side of the humidifier until some resistance is felt Then using an open end wrench on the reducer fitting screw the assembly 1 full turn to fully tighten it DO NOT tighten the filter strainer by gras...

Страница 13: ...correct electrical wire sizing from the control panel to the humidifiers for three different distances All wire sizes listed are for stranded THHN or NTW wire only Do not use solid conductor wire For...

Страница 14: ...Operation 1 Turn the main power source switch on the control box to the On position 2 Open the water supply valve allowing water to flow to the humidifier 3 Perform a manual drain cycle to flush any...

Страница 15: ...teps for Long Term Shutdown If the humidifier is not signalled to turn On for a period of three days the level control board will automatically signal the humidifier to operate a drain cycle When oper...

Страница 16: ...ch to Off and close the water supply valve WARNING Turn off power to the unit unless you are performing tests that require power With power and controls energized the unit could begin operating automa...

Страница 17: ...Cycle Description Necessary Tools Phillips screwdriver Air filter cleaning About once a week depending on the extent of contamination The interval should be short ened if environmental condi tions are...

Страница 18: ...ontrol box disconnect switch to Off and close the water supply valve 2 Loosen the bowl on the filter strainer assembly and remove it Photo 3 3 Remove the element and rinse the filter and the inside of...

Страница 19: ...cement 4 2 4 Float Switches 1 Loosen and remove the float panel mounting screws 2 Pcs Photo 8 Note Don t let the screws drop into the tank 2 Lift the float panel out and turn it over Photo 9 3 Check f...

Страница 20: ...the air flow guide Photo 13 4 Check the water tank interior for contamination Wipe and clean the water tank interior and clean the surface of the transducers etc in the water tank by wiping with a sof...

Страница 21: ...through the above checking remove the mist guide cover and air flow guide and check the interior of the water tank 4 3 Troubleshooting and Repair Should any failure occur make the necessary repairs re...

Страница 22: ...ply system overflowing Water supply solenoid valve is faulty Overflowing occurs even after power is turned off 4 Consumable parts Fan lead wires are loose or disconnected from the terminals Clean the...

Страница 23: ...ing the parts Photo 19 6 The transducers are visible when you rotate the tank to view the bottom Photo 20 7 The nebulizer print plates are on the side of the tank adjacent to the transducers Photo 21...

Страница 24: ...re ties bundling the sensor cable and unscrew the sensor wires from the terminal connectors on the printed circuit board 3 Connect the new sensor wires to the printed circuit board 4 Install the new s...

Страница 25: ...e the nuts to mount the new part Photo 27 5 Clean the spacer o ring groove and o ring 6 Assemble the new transducer with the spacer and o ring and install them with the saved mounting screws Photo 28...

Страница 26: ...laced it is recommended that the transducer be replaced also 6 Referring to Sect 4 4 2 Re assembling re assemble the unit by reversing the procedure described in Section 4 4 1 4 4 6 Water Solenoid Val...

Страница 27: ...rd remove the lead wire terminal connectors 3 Pcs from the board see Photos 6 7 Note Grasp the connectors when removing Never pull the lead wires 10 Slide the level control board out along the guides...

Страница 28: ...n UPS ground the customer is responsible for the shipping charges If you do not have established credit with STULZ you must give a freight carrier account number A written or faxed purchase order is r...

Страница 29: ...DRAWINGS 6 1 Layout Drawing of Humidifier Covers Removed to Show Parts 1 4 2 8 7 6 5 3 The bubble numbers in the drawing coincide with the item numbers listed below 1 Drain Stub 1 8 NPT 2 Water Supply...

Страница 30: ...L NC NO C L M DC DC SolidState Relay 4 3 X 1 X2 PCB Level Controller X1 2 X1 3 X1 5 X2 1 X2 2 X2 3 X2 4 X2 5 X2 6 X2 7 X2 8 X3 1 X3 2 X3 3 X3 4 X3 5 X3 6 X1 6 X1 7 X1 4 X1 8 From Control Box Nebulize...

Страница 31: ...lve Solenoid DrainValve Solenoid Fan HighLevel Switch LowLevel Switch OverTemp Sensor BLUE RED X1 1 X X 2 1 X 1 X 2 Current ofRelay 5A 10 12A 1 2 2 1 PinNumber 4 X1 2 X1 3 X1 1 X1 4 X1 2 X1 3 X1 Conne...

Страница 32: ...2013 DRH Series GEN1 Ultrasonic Humidifier Installation Operation Maintenance Manual OUD0077D April 2013 DRH Series GEN1 Installation Operation Maintenance Specifictions are subject to change without...

Отзывы: