DRH Series GEN1 Ultrasonic Humidifi er Installation, Operation & Maintenance Manual

3-1

3.0  

OPERATION

3.1  Purge the Water Line

Before operating the unit, metal shavings or debris that may form during the installation process must be 
fl ushed from the water supply piping. Perform the following steps before allowing water to fl ow into the 
humidifi er:

1.  Ensure the main disconnect switch from the control box is set to “Off” for safety.

2.  With the water supply valve closed, disconnect the supply tubing from the fi lter strainer in the side of the unit.

3.  Open the supply valve and fl ush the tubing into a bucket or building drain for about 30 seconds. 

4.  After the water line is purged, close the valve and reconnect the supply line to the inlet fi lter/strainer.

3.2   Initial Operation Checklist

For new installations, ensure the unit is ready to operate by going through the following checklist prior to start-up:

1. The humidifi er is installed horizontally and level. 

2.  No obstacle is within 15 feet in front of the atomizing direction. 

3.  The electrical wiring is correctly connected. 

4.  De-ionized or reverse osmosis water supply is used. 

5.  The water supply piping and overfl ow piping are correctly connected and secured. 

6.  All parts are correctly installed. 

After the above items are checked, operation may begin.

3.3   Procedure for Operation 

1.  Turn the main power source switch on the control box to the “On” position. 

2.  Open the water supply valve allowing water to fl ow to the humidifi er. 

3.  Perform a manual drain cycle to fl ush any particulates from the tank utilizing the system controller (see 

STULZ Ultra-Series controller IOM manual #OUU0078, Section 5.5.1.2). 

4.  Set the humidity setpoint to the desired humidity level. 

5.  When power is supplied to the humidifi er and there is a demand for humidifi cation, water fl ows into the unit. 

When the water in the tank reaches the required level, the ultrasonic nebulizers will start producing mist.

6.  If the unit does not start operating, increase the humidity setpoint to create a demand for humidifi cation. 

7.  During operation, the humidifi er starts and stops by means of a signal from the control box.

8.  The water level in the water tank is maintained by the level controller.

9. If the water level in the tank falls below the safety level for any reason during operation, power to the 

ultrasonic nebulizers is cut off by the level controller.

After operation is started, check the following items on a regular basis:

 

Atomized mist is visible through all the mist blow tubes.

 

Check the humidifi er parts, overfl ow pipe and other piping for signs of leaking water.

 

Change the humidity setpoint to ensure the control box is interconnected properly and that it controls the  

 

operation of the humidifi er.

 

Check to see that the mist diffusion is good and that objects in the room or any obstacle are not directly    

 

exposed to the mist.

Содержание DRH-04

Страница 1: ...April 2013 DRH Series GEN1 Ultrasonic Humidifier Installation Operation Maintenance Manual MODELS DRH 04 DRH 08 DRH 06 DRH 16 READ AND SAVE THESE INSTRUCTIONS LIRE ET CONSERVER CES INSTRUCTIONS...

Страница 2: ...ntains confidential and proprietary information of Stulz Air Technology Systems Inc Distributing or photocopying this document for external distribution is in direct violation of U S copyright laws an...

Страница 3: ...1 3 3 Procedure For Operation 3 1 3 4 Precautions 3 2 3 5 Steps for Long Term Shutdown 3 2 4 0 Maintenance Repairs 4 1 4 1 Periodic General Maintenance 4 1 4 1 1 General 4 1 4 2 Maintenance Items and...

Страница 4: ...mation A bold text NOTE marks a short message in the information to alert you to an important detail A bold text CAUTION safety alert appears with infor mation that is important for protecting your eq...

Страница 5: ...g of the air inlet The humidifier may be filled with the condensed mist and electrical shorts may result CAUTION Observe the unit for water leakage A short circuit could occur if the humidifier is spl...

Страница 6: ...original warranty period or for 90 days from the date of installation whichever is greater Stulz Air Technology Systems Inc s warranty does not cover failures caused by improper installation abuse mis...

Страница 7: ...r supply temperature 40 F to 104 F Parts to be provided by user DI or RO supply water Water supply valve Water supply tubing 1 4 stainless steel or poly tubing rated for DI water power supply wiring a...

Страница 8: ...he water level is near an unsafe level and is closed when the water level is at a minimal level 1 6 5 Fan The 24VDC fan or fans both lightly pressurizes the air above the water to provide a path for t...

Страница 9: ...proportional signal is greater than 10 of the maximum input the microprocessor will turn the Solid State Relay on and off in a pulse width modulation control The period of the pulse width is 1 second...

Страница 10: ...l Avoid dropping or jarring the unit to prevent damage to the internal parts The unit should always be stored in a dry location prior to installation A Data Package has been sent with your unit It con...

Страница 11: ...ht of the unit Weight estimates can be found on the installation drawing provided with your unit Secure the unit with fasteners field supplied by others so that it will not move during operation Ensur...

Страница 12: ...side of the humidifier until some resistance is felt Then using an open end wrench on the reducer fitting screw the assembly 1 full turn to fully tighten it DO NOT tighten the filter strainer by gras...

Страница 13: ...correct electrical wire sizing from the control panel to the humidifiers for three different distances All wire sizes listed are for stranded THHN or NTW wire only Do not use solid conductor wire For...

Страница 14: ...Operation 1 Turn the main power source switch on the control box to the On position 2 Open the water supply valve allowing water to flow to the humidifier 3 Perform a manual drain cycle to flush any...

Страница 15: ...teps for Long Term Shutdown If the humidifier is not signalled to turn On for a period of three days the level control board will automatically signal the humidifier to operate a drain cycle When oper...

Страница 16: ...ch to Off and close the water supply valve WARNING Turn off power to the unit unless you are performing tests that require power With power and controls energized the unit could begin operating automa...

Страница 17: ...Cycle Description Necessary Tools Phillips screwdriver Air filter cleaning About once a week depending on the extent of contamination The interval should be short ened if environmental condi tions are...

Страница 18: ...ontrol box disconnect switch to Off and close the water supply valve 2 Loosen the bowl on the filter strainer assembly and remove it Photo 3 3 Remove the element and rinse the filter and the inside of...

Страница 19: ...cement 4 2 4 Float Switches 1 Loosen and remove the float panel mounting screws 2 Pcs Photo 8 Note Don t let the screws drop into the tank 2 Lift the float panel out and turn it over Photo 9 3 Check f...

Страница 20: ...the air flow guide Photo 13 4 Check the water tank interior for contamination Wipe and clean the water tank interior and clean the surface of the transducers etc in the water tank by wiping with a sof...

Страница 21: ...through the above checking remove the mist guide cover and air flow guide and check the interior of the water tank 4 3 Troubleshooting and Repair Should any failure occur make the necessary repairs re...

Страница 22: ...ply system overflowing Water supply solenoid valve is faulty Overflowing occurs even after power is turned off 4 Consumable parts Fan lead wires are loose or disconnected from the terminals Clean the...

Страница 23: ...ing the parts Photo 19 6 The transducers are visible when you rotate the tank to view the bottom Photo 20 7 The nebulizer print plates are on the side of the tank adjacent to the transducers Photo 21...

Страница 24: ...re ties bundling the sensor cable and unscrew the sensor wires from the terminal connectors on the printed circuit board 3 Connect the new sensor wires to the printed circuit board 4 Install the new s...

Страница 25: ...e the nuts to mount the new part Photo 27 5 Clean the spacer o ring groove and o ring 6 Assemble the new transducer with the spacer and o ring and install them with the saved mounting screws Photo 28...

Страница 26: ...laced it is recommended that the transducer be replaced also 6 Referring to Sect 4 4 2 Re assembling re assemble the unit by reversing the procedure described in Section 4 4 1 4 4 6 Water Solenoid Val...

Страница 27: ...rd remove the lead wire terminal connectors 3 Pcs from the board see Photos 6 7 Note Grasp the connectors when removing Never pull the lead wires 10 Slide the level control board out along the guides...

Страница 28: ...n UPS ground the customer is responsible for the shipping charges If you do not have established credit with STULZ you must give a freight carrier account number A written or faxed purchase order is r...

Страница 29: ...DRAWINGS 6 1 Layout Drawing of Humidifier Covers Removed to Show Parts 1 4 2 8 7 6 5 3 The bubble numbers in the drawing coincide with the item numbers listed below 1 Drain Stub 1 8 NPT 2 Water Supply...

Страница 30: ...L NC NO C L M DC DC SolidState Relay 4 3 X 1 X2 PCB Level Controller X1 2 X1 3 X1 5 X2 1 X2 2 X2 3 X2 4 X2 5 X2 6 X2 7 X2 8 X3 1 X3 2 X3 3 X3 4 X3 5 X3 6 X1 6 X1 7 X1 4 X1 8 From Control Box Nebulize...

Страница 31: ...lve Solenoid DrainValve Solenoid Fan HighLevel Switch LowLevel Switch OverTemp Sensor BLUE RED X1 1 X X 2 1 X 1 X 2 Current ofRelay 5A 10 12A 1 2 2 1 PinNumber 4 X1 2 X1 3 X1 1 X1 4 X1 2 X1 3 X1 Conne...

Страница 32: ...2013 DRH Series GEN1 Ultrasonic Humidifier Installation Operation Maintenance Manual OUD0077D April 2013 DRH Series GEN1 Installation Operation Maintenance Specifictions are subject to change without...

Отзывы: