9.4.7.5
Contacts activated by an event {14077} {14129}
Different states and events within the installation can be used to activate the auxiliary contacts. The
events can be combined with each other to create complex functions.
9.4.7.5.1
VarioString is ON {14188} {14189} (no)
The contact is activated if the VarioString is switched ON.
9.4.7.5.2
VarioString is OFF {14078} {14130} (no)
The contact is activated if the VarioString is switched OFF.
9.4.7.5.3
Remote entry (AUX 1) {14214}{14215}( (no) (available as from software version 1.5.22)
The contact is activated depending on the state of the remote entry.
9.4.7.5.4
Battery undervoltage {14079} {14131} (no)
The contact is activated in the event of battery undervoltage.
9.4.7.5.5
Battery overvoltage {14080} {14132} (no)
The contact is activated in the event of battery overvoltage.
9.4.7.5.6
Earth fault {14081} {14133} (no)
The contact is activated in the event of an earth fault.
9.4.7.5.7
PV error (48h without charge) {14082} {14134} (no)
The contact is activated in case the battery has not been charged in the last 48 hours.
9.4.7.5.8
Overtemperature {14083} {14135} (no)
The contact is activated in the event of over temperature of the device.
9.4.7.5.9
Bulk charge phase {14084} {14136} (no)
The auxiliary contact is activated if the battery is charging in the bulk phase.
9.4.7.5.10
Absorption phase {14085} {14137} (no)
The auxiliary contact is activated if the battery is charging in the absorption phase.
9.4.7.5.11
Equalization phase {14086} {14138} (no)
The auxiliary contact is activated if the battery is charging in the equalization phase.
9.4.7.5.12
Floating phase {14087} {14139} (no)
The auxiliary contact is activated if the battery is charging in the floating phase.
9.4.7.5.13
Reduced floating phase {14088} {14140} (no) and
9.4.7.5.14
Periodic absorption phase {14089} {14141} (no)
You can activate the auxiliary contacts on the reduced floating phase and periodic absorption
phase in presence of an Xtender and synchronised with the battery cycle.
9.4.7.6
Contacts activated by the battery voltage {14090} {14142}
These parameters activate the auxiliary contacts if the voltage drops below a pre-defined voltage level during
a set period. It is possible to define three voltages linked with three periods to activate the auxiliary contact.
The auxiliary contact will only become deactivated when the battery has risen above a certain
voltage and a certain period, both values independent of the activation parameters.
This voltage and time period for deactivation is also programmable.
Содержание VarioString VS-120
Страница 2: ...Studer Innotec SA VarioString 2 V 2 3 User manual ...
Страница 13: ...Studer Innotec SA VarioString User manual V 2 3 13 4 1 2 VarioString VS 120 ...
Страница 61: ...Studer Innotec SA VarioString User manual V 2 3 61 ...
Страница 62: ...Studer Innotec SA VarioString 62 V 2 3 User manual ...
Страница 63: ...Studer Innotec SA VarioString User manual V 2 3 63 ...