TROUBLE-SHOOTING
User
ref.
Description
Troubleshoot
0 Warning (000): Battery low
The battery voltage has fallen below the
battery undervoltage level {14216}. The
device will not turn off.
12 (012): Use of battery temperature sensor
Indicates the presence of a BTS-01
temperature probe connected to the device
that sent the message.
14 Halted (014): Over temperature EL
The device is stopped after surpassing the
max internal electronics temperature.
16 Warning (016): Fan error detected
Every 60 seconds a test is performed to
confirm the presence of the external fan
(ECF-01). If it is suddenly not detected, due
to a hardware problem or if it is removed
manually, this message appears.
20 Halted (020): Battery overvoltage
Battery overvoltage
80 Halted (080): No battery (or reverse polarity) The battery voltage must be greater than 3V
in order for it to be detected.
81 Warning (081): Earthing fault
An earth fault has been detected. For systems
with an earthed pole, this indicates a voltage
difference between earth and the pole
greater than the allowed value. For floating
systems, this indicates a voltage difference
between earth and a pole that is less than the
allowed value.
84 (084): Equalization performed
Sent when the equalization phase has finished
correctly. The message is not sent when the
absorption or floating phases are forced in
order to exit the equalization phase.
138 Error (138): XT master synchronization lost
Message sent if the synchronization with the
XT has not been received within 10s.
140 (140): Synchronized on XT master
Message sent after receiving the first frame
of synchronization with XT.
150 Error (150): Cabling error between PV and
VarioString
Check that the cable connections of the PV
modules corresponds to the type of cabling
set in parameter settings.
168 (168): Synchronized with VarioString master
Sent after receiving the first frame of
synchronization with VS.
169 (169): Synchronization with VarioString master
lost
Sent if the synchronization with the VS has not
been received in the past 10s.
170
171
Warning (170): No solar production in the last
48h on PV1
Warning (171): No solar production in the last
48h on PV2
Check that the PV modules are connected
correctly and the state of protection
equipment (fuses and circuit breakers).
180 (180): Command entry activated
When parameter {14205} is used, a message
is sent in the event of activation of the
remote entry.
211 (211): Command entry deactivated
When parameter {14205} is used, a message
is sent in the event of deactivation of the
remote entry.
213 (213): Battery current limitation by the BSP
stopped
Message sent by master 2 seconds after
stopping to receive a signal for limiting the
current from the BSP.
Содержание VarioString VS-120
Страница 2: ...Studer Innotec SA VarioString 2 V 2 3 User manual ...
Страница 13: ...Studer Innotec SA VarioString User manual V 2 3 13 4 1 2 VarioString VS 120 ...
Страница 61: ...Studer Innotec SA VarioString User manual V 2 3 61 ...
Страница 62: ...Studer Innotec SA VarioString 62 V 2 3 User manual ...
Страница 63: ...Studer Innotec SA VarioString User manual V 2 3 63 ...