Studer Innotec SA
VarioString
User manual
43
The programming of each
contact
is
made
independently. The auxiliary
contacts are activated and
deactivated with a 2 second
delay to avoid too frequent
switching.
The auxiliary contacts react to
different types of signals,
graphically illustrated below.
Basic events that activate the
contacts are:
Simple events
Scheduled events
Levels
In the following descriptions,
each parameter has two
reference
numbers.
The
reference number on the left
refers to the auxiliary contact 1
and the reference number on
the right refers to the auxiliary
contact 2. ({reference auxiliary
contact 1} {reference auxiliary
contact 2}).
9.4.7.1
Operating mode {14071} {14123} (automatic)
The auxiliary contact can be controlled in 4 different ways:
Manual ON: in this mode, the contact is permanently activated "ON" whatever the external
conditions or programming.
Manual OFF: in this mode, the contact is permanently deactivated "OFF" whatever the external
conditions or programming.
Automatic: in this mode the auxiliary contact is activated according to the conditions and restrictions
of its programming.
Reversed automatic: in this mode, the conditions and restrictions define the deactivation of the relay.
9.4.7.2
Combination of the events for the auxiliary contact {14072} {14124} (first active (OR))
This parameter defines how various events intended to activate the auxiliary contact are combined.
The contact can be activated either by a single event (OR function) or by all events being fulfilled
at the same time (AND function).
9.4.7.3
Contacts activated in night mode {14073} {14125}
The auxiliary contact can be activated with the function "night mode". When the “night mode” is
activated and the activation delay is up, the auxiliary contacts will be active for a predefined time
period. If the activation time is set to zero, the auxiliary contact will remain permanently activated
until the end of the night mode.
Activated in night mode {14074} {14126} (no)
Delay of activation after entering night mode {14075} {14127} (1 min)
Activation time for the auxiliary relay in night mode {14076} {14128} (1 min)
9.4.7.4
Contact active with a fixed time schedule {14206} {14210} (menu)
The auxiliary contacts can be activated with a fixed time schedule. Once the mode "Fixed time
schedule" is activated and it is past the start hour, the auxiliary contacts will be active until it is past
the set end hour.
Contact activated with fixed time schedule (AUX1) {14207} {14211} (no)
Start hour (AUX1) {14208} {14212} (hh:mm)
End hour (AUX 1) {14209} {14213} (hh:mm)
{14072}
{14071}
{14124}
{14123}
Содержание VarioString VS-120
Страница 2: ...Studer Innotec SA VarioString 2 V 2 3 User manual ...
Страница 13: ...Studer Innotec SA VarioString User manual V 2 3 13 4 1 2 VarioString VS 120 ...
Страница 61: ...Studer Innotec SA VarioString User manual V 2 3 61 ...
Страница 62: ...Studer Innotec SA VarioString 62 V 2 3 User manual ...
Страница 63: ...Studer Innotec SA VarioString User manual V 2 3 63 ...