Studer Innotec SA
VarioString
User manual
51
12.3
V
ARIO
S
TRING
VS-70
+
RCC-02
12.4
C
OMMENTS ON THE WIRING EXAMPLES
11.3
Elem. Description
Refer to
a
Remote control
b
Battery
See chap. 4.2
d
Lightning protection device
See chap. 4.5
e
Communication cable
See chap. 4.6
f
DC protection device
See chap. 4.2.3
T
Protective earth
*Main protective earth/protective equipotential bonding
connected to the conductive and accessible parts of the
building and if possible, connected to a standard earth
electrode.
T1
Protective earth for the
equipment
*The equipment is designed to be connected to a
protective earth (Class I) to which they must be connected.
T2
Protective earth for the
battery
*One of the battery poles must be grounded. The other
configurations must meet the recommendations at chap.
4.4.
T3
Protective earth for the solar
generator
*The protective earth for the PV generator and its lightning
protection device are connected separately to the main
protective earth (local equipotential bonding).
Содержание VarioString VS-120
Страница 2: ...Studer Innotec SA VarioString 2 V 2 3 User manual ...
Страница 13: ...Studer Innotec SA VarioString User manual V 2 3 13 4 1 2 VarioString VS 120 ...
Страница 61: ...Studer Innotec SA VarioString User manual V 2 3 61 ...
Страница 62: ...Studer Innotec SA VarioString 62 V 2 3 User manual ...
Страница 63: ...Studer Innotec SA VarioString User manual V 2 3 63 ...