9.4.2
Parameter access level
All described parameters are accessible through 2 different access levels, "Basic" and "Expert". When
using the factory configuration, only a few parameters are accessible at "Basic" level.
To access the other menus and parameters, the RCC's configuration must be set to “Expert” level. How
to change the user level is indicated in the RCC user manual, chapter "User level".
The parameters in grey "Installer" are accessible only by qualified personnel.
9.4.3
Organisation of the VarioString configuration menu
Level
User
ref. Parameter
Factory value
Basic
14000 BASIC SETTINGS
Expert 14174 Block manual programming (dip-switch)
No
Expert 14001 Battery charge current (VS-120)
120 Adc
Expert 14217 Battery charge current (VS-70)
70 Adc
Basic
14002 Configuration of PV modules (VS-120)
Automatic
Basic
14067 Restore default settings
-
Inst.
14068 Restore factory settings
-
Expert 14003 BATTERY MANAGEMENT AND CYCLE
Basic
14036 Synchronisation battery cycle with Xtender
Yes
Expert 14001 Battery charge current (VS-120)
120 Adc
Expert 14217 Battery charge current (VS-70)
70 Adc
Expert 14216 Battery undervoltage
40 Vdc
Expert 14035 Temperature compensation
-3 mV/°C/cell
Expert 14004 Floating phase
Expert 14005 Floating voltage
54.4 Vdc
Expert 14006 Force phase of floating
-
Expert 14007 Absorption phase
Expert 14008 Absorption phase allowed
Yes
Expert 14009 Absorption voltage
57.6 Vdc
Expert 14010 Force absorption phase
-
Expert 14011 Absorption duration
120 min
Expert 14012 End of absorption triggered by the current
No
Expert 14013 Current threshold to end absorption phase
10 Adc
Expert 14016 Equalization phase
Expert 14017 Equalization allowed
No
Expert 14018 Force equalization
-
Expert 14021 Equalization voltage
62.4 Vdc
Expert 14020 Equalization current
80 Adc
Expert 14022 Equalization duration
30 min
Expert 14023 Equalization with fixed interval
Yes
Expert 14024 Days between equalizations
26 days
Expert 14025 End of equalization triggered by the current
No
Expert 14026 Current threshold to end equalization phase
10 Adc
Expert 14019 Equalization before absorption phase
Yes
Expert 14027 New cycle
Expert 14028 Force a new cycle
-
Expert 14029 Voltage level 1 to start a new cycle
48.8 Vdc
Expert 14030 Time period under voltage level 1 to start a new cycle
30 min
Expert 14031 Voltage level 2 to start a new cycle
47.2 Vdc
Expert 14032 Time period under voltage level 2 to start a new cycle
2 min
Expert 14033 Cycling restricted
Yes
Expert 14034 Minimal delay between cycles
1 hours
Содержание VarioString VS-120
Страница 2: ...Studer Innotec SA VarioString 2 V 2 3 User manual ...
Страница 13: ...Studer Innotec SA VarioString User manual V 2 3 13 4 1 2 VarioString VS 120 ...
Страница 61: ...Studer Innotec SA VarioString User manual V 2 3 61 ...
Страница 62: ...Studer Innotec SA VarioString 62 V 2 3 User manual ...
Страница 63: ...Studer Innotec SA VarioString User manual V 2 3 63 ...