User manual
14.11.9
Contacts activated on battery state of charge (SOC) {1501} {1502}
(function active only with a BSP)
You can activate the auxiliary contacts according to the battery state of charge. If the battery state
of charge goes below a given threshold, the contact will be activated. A duration can be linked to
the threshold, which means that the battery state of charge must be below this threshold within the
choosen duration, before the contact is activated.
The contact is deactivated when the battery state of charge goes again below a specific threshold
that can be also linked to a duration.
The contact can also be deactivated when the battery reaches the floating phase.
Level SOC 1 active {1439} {1442}
Level SOC 1 {1440} {1443}
Duration 1 {1581} {1590}
Level SOC 2 active {1582} {1591}
Level SOC 2 {1583} {1592}
Duration 2 {1584} {1593}
Level SOC 3 active {1585} {1594}
Level SOC 3 {1586} {1595}
Duration 3 {1587} {1596}
Level SOC to deactivate the auxiliary contact {1441} {1444}
Duration on level for deactivation {1588} {1597}
Deactivate if the battery is in floating phase {1589} {1598}
14.11.10
Security: Limit the time of activation {1512} {1513}
Caution :
If the maximum duration for the relay activation that you have selected is reached
and if the activation conditions are still present (for instance a battery undervoltage),
the contact will not be reactivated as long as the conditions are present
. Therefore
there is a risk that the auxiliary contact remains locked in this deactivated state and
you will have to reset manually this alarm by deactivating and then activating this
parameter.
Use this function with care and only as a security.
14.11.11
Maximum duration of activation {1514} {1515}
When the conditions are met, either one or two relays are activated permanently. If you wish that
the activation duration is limited in time, even if the conditions are met, you can activate this function.
Once the relay is activated, a countdown runs according to the duration you have selected. Once
this countdown is completed the relay is released, even if the conditions are still there. The relay can
not be anymore activated as long as the activation conditions have not disap-peared.
14.11.12
Reset all settings {1569} {1570}
This function serves to reset all previous settings done on the corresponding auxiliary contact. Once
this operation done, the auxiliary contact is not activated anymore.
Caution: this function cannot be cancelled.
Use this function before programming any function for an auxiliary contact. By doing
this way you are sure that you begin with no unexpected setting who can activate
the contact.