Studer Innotec SA
RCC-02/-03
32
User manual
12.8
(015)
H
ALTED
:
I
NVERTER OVERLOAD
BL
The users need more power than the Xtender inverter can supply.
Method:
adapt the power max. of the users to the power max. of the Xtender.
12.9
(016)
W
ARNING
:
F
AN ERROR DETECTED
A dysfunction of the ventilation has been detected; get it checked by a technical staff.
12.10
(018)
W
ARNING
:
E
XCESSIVE BATTERY VOLTAGE RIPPLE
The voltage ripple at the battery cables is too high.
Solution:
Check that the battery cable section is correct.
Check the tightness of the battery cables.
Check that the charge current matches your battery.
Check the state of your batteries.
The use of batteries of an inappropriate capacity may also cause this error message.
In this case, reduce the charge current or lower the power output of the consumers.
The voltage ripple on the batteries may be caused by their ageing. In this case, lower
the charge current.
12.11
(019)
H
ALTED
:
B
ATTERY UNDER VOLTAGE
The functions inverter and Smart-Boost of the Xtender are deactivated because the batteries are
discharged.
Method: recharge your batteries to reactivate these functions automatically.
12.12
(020)
H
ALTED
:
B
ATTERY OVERVOLTAGE
The voltage of the battery at the Xtender DC input is too high. The system is stopped for security
reasons.
Method: check that the battery nominal voltage suits the Xtender one.
In case of an external charger, check that it charges the batteries with a voltage suitable for the
Xtender.
Dans le cas d’un fonctionnement avec des générateurs solaires, vérifiez que le
système ne fonctionne pas sur les panneaux sans batterie et vérifiez l’état du
régulateur de charge
12.13
(021)
I
NPUT LIMIT REACHED
,
NO TRANSFER
The power output of the consumers exceeds the one specified for the source, and the transfer relay
cannot be activated. The Xtender operates in inverter mode.
This situation occurs only if you have deactivated the parameter {1436} Solution:
Check that the configuration of the maximum current for the source {1107} corresponds to
the maximum current of the source connected at AC-In.
Reduce the number or power output of the consumers.
In this case, the transfer relay is not activated and the recharging of the batteries
cannot take place. If this situation continues, you might discharge your batteries.