Sensors
The following temperature sensors have been fitted in the boiler (S1 and S2 on the rear / right-side of the heat-
exchanger and one for each burner):
S1
=
Flow temperature sensor (orange wire)
S2
=
Return temperature sensor (green wire)
S3
=
External flow temperature sensor
S4
=
Calorifier/tank temperature sensor (if connected)
S5
=
Outside temperature sensor (if connected)
S6
=
Flue sensor (white wire)
(S3¹)
=
if terminals S3 are not connected, the average value of S1 top and S1 bottom is
taken and this value will be displayed.
The sensors used in the boilers are of the NTC (negative temperature coefficient) type and have the following
properties:
SENSOR
SENSOR TYPE
SENSOR VALUE
S1
Internal flow sensor
NTC-10K-B3977
S2
Internal return sensor
NTC-10K-B3977
S3
External flow sensor
NTC-10K-B3977
S4
Calorifier/tank sensor
NTC-10K-B3977
S5
Outdoor sensor
NTC-12K-B3740
S6
Flue gas sensor
NTC-10K-B3975
Conversion table temperature vs. resistance except outside sensor. NTC-10k B3977 (B3975)
Temperature
(°C)
Resistance
(Ω)
Temperature
(°C)
Resistance
(
Ω)
Temperature
(°C)
Resistance
(
Ω)
Temperature
(°C)
Resistance
(
Ω)
-30
175203
20
12488
70
1753
120
387
-25
129289
25
10000
75
1481
125
339
-20
96360
30
8059
80
1256
130
298
-15
72502
35
6535
85
1070
135
262
-10
55047
40
5330
90
915
140
232
-5
42158
45
4372
95
786
145
206
0
32555
50
3605
100
677
150
183
5
25339
55
2989
105
586
155
163
10
19873
60
2490
110
508
160
145
15
15699
65
2084
115
443
165
130
Conversion table temperature vs. resistance outside sensor. NTC-12k B3740
Temperature
(°C)
Resistance
(Ω)
Temperature
(°C)
Resistance
(
Ω)
-50
0
36130
-45
5
28600
-40
10
22800
-35
15
18300
-30
171800
20
14770
-25
129800
25
12000
-20
98930
30
9804
-15
76020
35
8054
-10
58880
40
6652
-5
45950
45
5522