9
Type boiler
S-CB
+
400
S-CB
+
550
EMISSION
[EN437]
Nominal value at min. max. load
CO
2
flue gas G25.3, G20 min-max
%
9,0- 9,0
CO
2
flue gas G31, G30, B/P min-max
%
10,0-10,5
NO
x
class [EN483/ EN15420]
-
6
Flue gas temperature at atmospheric tempera-
ture of 20°C
°C
90
Mass flow flue gas [min-max]
Q
fluegas
condensing
g/s
24,1 - 207,8
33,1 - 285,7
Available pressure for the flue system
4
Pa
200
Available pressure for the flue system with speci-
fied Concentric Roof Terminal
4
Pa
250
INSTALLATION
Hydraulic resistance of the
boiler
T = 20 K
mWK
4,0
4,1
T = 25 K
mWK
2,6
2,8
Water pressure boiler min-max.
bar
1,0
– 4,0
5
Maximum flow temperature
°C
85
ELECTRICAL
Power supply / frequency
V / Hz
230 (400
6
) / 50
Maximum power consumption (exclusive pump)
W
960
Max. current P1 pump relay (I nom)
A
9
Protection class
IPX0B
NOTES
4
Maximum combined resistance of flue gas
and air supply piping at high fire.
5
With the standard built-in pressure sensor
replaced by a pressure switch, pressure
may go up to 6.0 bar. Parameter P4AD
needs to be changed.
6
230 Vac is necessary for the boiler to func-
tion. If a 400 Vac boiler pump is applied, 400
Vac must be connected to the appliance so
the power supply for the pump can be deliv-
ered by the system. (An optional safety
switch for the pump motor must be added ex-
ternally).