86
11.2.6 0-10
VDC
REMOTE BURNER INPUT CONTROL
The burner input is controlled by connecting an external 0-10 VDC signal to the boiler (connections 15-16).
P5 BB
Analogue input Config (0=off 1=temp 2=power) (display D1).
This parameter must be set at "2" so the supplied 0-10V dc signal will control the burner input. The standard factory
setting is
‘1’, temperature set point control. Possible settings are:
0 =
0-10V control off
1 =
0-10V temperature set point control active
2 =
0-10V burner input control active
See also the following graph for the relation between the burner input and the control signal.
Curve and values only for illustration purposes, programmed parameter values can deviate!
11.2.7
TIMER CONTACT FUNCTION
This function can be activated when using an external night reduction timer for heating. This timer contact can be
connected to the thermostat terminals (connections 13-14).
P5 AB
Timer Contact (1=on) (display A9).
When this parameter is activated and:
- The thermostat terminals are bridged (timer contact closed) the normal daytime temperature is used as set point.
- The thermostat terminals are not bridged (timer contact open) the night reduced temperature is used as set point.
0-10 Vdc control signal
bu
rne
r
inp
ut
[%]
P2GB off
P2GA on
P2GC max.
Min. burner input %
fixed value, e.g. 25%