9.4
Connecting the power supply and boiler pump P1, 230V/1~ or 400V/3~
•
Connect the power supply to the connecting block on the front top side of the unit. See figure below.
•
A 230V/1~ pump
must be connected to the relay besides the power supply connectors, according to the top
figure below.
A 400V/3~ pump
must be connected to the relay besides the power supply connectors, according to the
bottom figure below.
•
Connection of the 230 V AC power supply to the control panel has already been mounted in the factory.
•
Preferably an external isolation switch should be connected to work safe on the boiler. The connection needs
to be fused with a maximum 16 A fuse.
•
When a pump motor safety circuit is required, this should be added externally from the boiler. Another option
is to use a pump with an internal electronic safety circuit. Maximum operational switch current for the pump
relay is 9 A per phase.
Connecting a 230V/1~ pump:
Power supply
1~230V/50Hz
N/GND
Boiler pump
1~230V/50Hz
N/GND
Connecting a 400V/3~ pump:
Power supply
3~400V/50Hz
N/GND
Boiler pump
3~230V/50Hz
GND
All electrical connections must be installed according to all applicable regulations.
CAREFUL: When the boiler is switched off, electrical power might still be present at the connectors and relay
shown above. We advise to add an external service switch to shut off all the power to the boiler while working
on it.
connecting block
connecting block