56
10.7
Programming in standby mode
Standby
Use the standby mode for modifying boiler settings without interaction with the boiler control. Changes are effectu-
ated at leaving standby mode.
Properties of standby mode:
•
Keys are active and the menu is accessible.
•
Burners do NOT respond to an external heat demand.
•
All control functions are ON: pumps, fans and cascade are operational, recirculation and frost protection
are both active.
How to program the boiler:
•
Disconnect or shut down the room thermostat and/or other external controllers from the boiler. The CH
pump and fan will stop after a short time.
•
Switch the boiler in standby mode by pressing [ON/OFF] for three seconds.
•
The next display screen should appear:
Display message
H E A T I N G : b o i
l e r
o f f
> > > : 1 2 3 . 4 ° C ( 1 2 3 . 4 ° C )
•
Program the boiler at the control panel (see the following sections).
•
Terminate programming mode by pressing [MENU], or [ENTER] and NO
◄ or YES ►.
•
Reactivate the boiler by pressing [ON/OFF] for three seconds again.
10.8
Setting the time & date
The following graphs describe how to program the time and date of the unit.
Operating screen:
H E A T I N G : b o i l e r
o f f
> > > : 1 2 3 . 4 ° C ( 1 2 3 . 4 ° C )
Press [MENU]
Main menu screen:
M a i n M e n u
C l o c k
The display shows "CLOCK" press [ENTER]
Setting Time and Date:
S e t
t i m e / d a t e 0 8 : 3 3
3 0 / 0 3 / 2 0 1 0 T u e
The day is now blinking/selected and can be changed.
Use [▲]& [▼] to change the value.
Use [◄] & [►] to select another value.
Press [ENTER] for the confirmation screen after all changes
are done.
Confirmation screen:
A r e y o u
s u r e
< C a n c e l
;
> C o n f i r m
Press [
◄
] to cancel the changes made (display goes back to
operating screen).
Press [
►
] to confirm the changes made. The time and day will
start blinking for a few seconds. After this, the display returns
to its operating screen.