Operating instruction Z7510 Multizone temperatur controller
I
Temperatur controller
42
STRACK NORMA GmbH & Co. KG · Königsberger Str. 11 · D-58511 Lüdenscheid · Tel +49 2351 8701-0 · www.strack.de
08.2018
Operations manual NR4000-v.2
42
During the softstart phase, autotuning can not be
activated.
If a setpoint gradient is programmed, it is also not
active during the softstart.
The softstart works, if
- the controller is switched on and the actual tem-
perature is below the softstart setpoint minus 5%
of the range (e.g. range: 400°C -> 5%= 20°C).
- the parameter „1 P“ (prop. band, xp) is program-
med > 0,1%.
The softstart can be activated and programmed for
every zone individually.
- Setpoint limitation:
Highest adjustable setpoint
max. setpoint
value (
factory default: 400°C
)
- Setpoint limitation:
Lowest adjustable setpoint
min. setpoint
value (
factory default: 0°C
)