Defrosting control circuit 1
Para-
meter
Description of function
Setting range
Values
default
Assignment of evaporation sensors
(defrosting sensors)
detailed description of sensors in parameters
through
0: none
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: weighted mean value from
F1 and F2
2
Defrosting interval
0: no automatic defrosting
1...99 hrs.
8
Type of defrosting
0: no defrosting
1: compressor off only (circulating air)
2: electrical
3: with hot gas
2
Stop at defrosting temperature
0 ... +30.0°C
10.0
Defrosting time limitation
1...99 min.
30
Display of cold store temperature during
defrosting
0: normal
1: last temperature before defrosting
1
Temperature difference to cold store setpoint
in previous cooling
-15°C ... 0.0°C
0.0
Time limitation in previous cooling
1 ... 180 min.
10
Delay of start of defrosting after compressor
off
=2
0 ... 900 sec.
60
Dripping time
0 ... 15 min.
1
Stop delay drip tray heating
0 ... 60 min.
10
Password of parameter level
-99 ... 999
0
Fan control circuit 1
Para-
meter
Description of function
Setting range
Values
default
Fan speed control mode, Set1
0 ... 100%
80.0
Fan speed defrosting, Set1
0 ... 100%
80.0
Fan speed control mode, Set2
0 ... 100%
100
Fan speed defrosting, Set2
0 ... 100%
100
Start-up time
0 ... 60 sec.
5
Minimum speed
(output variable if result=0)
0 ... 100%
10.0