Order no.: 900312.001
V2.0
Page 35
Details Status 1
Bit Status 1
Value=0
Value=1
R/W
15
14
13
12
11
10
9
8
7
6
5
4
3
Reset MAX memory
R
2
Reset MIN memory
R
1
Nachtschaltung aktiv
no
yes
R
0
Set 2 active
no
yes
R
Writing to Bits that are READ ONLY will be ignored; Bits not used are reading always Zero.
Details Status 2
Bit Status 2
Value=0
Value=1
R/W
15
14
Nominal: drip tray heating
inactive
active
R
13
Nominal: defrosting circuit 2
inactive
active
R
12
Nominal: control contact circuit 2
inactive
active
R
11
Nominal: condenser fan
inactive
active
R
10
Nominal: evaporator fan
inactive
active
R
9
Nominal: defrosting circuit 1
inactive
active
R
8
Nominal: compressor
inactive
active
R
7
6
Actual: drip tray heating
inactive
active
R
5
Actual: defrosting circuit 2
inactive
active
R
4
Actual: control contact circuit 2
inactive
active
R
3
Actual: condenser fan
inactive
active
R
2
Actual: evaporator fan
inactive
active
R
1
Actual: defrosting circuit 1
inactive
active
R
0
Actual: compressor
inactive
active
R
Writing to Bits that are READ ONLY will be ignored; Bits not used are reading always Zero.