Order no.: 900312.001
V2.0
Page 17
Control circuit 2
(password-protected)
Para
meter
Description of function
Setting range
Values
default
Assignment of sensors to control circuit 2
detailed description of sensors in parameters
through
0: none
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: weighted mean value from
F1 and F2
0
2nd control circuit: setpoint
...
10.0
2nd control circuit: abs. setpoint or DeltaW
0: absolute
1: DeltaW
1
2nd control circuit: switching mode
0: heating
1: refrigerating
1
2nd control circuit: hysteresis
0.1...99.0°C
2.0
2nd control circuit: hysteresis mode
0: symmetrical
1: one-sided
1
Upper setpoint limit
... +999°C
50.0
Lower setpoint limit
-99°C ...
-50
Function in the case of sensor fault
0: contact off
1: contact on
1
Defrosting interval control circuit 2
0: no defrosting
1...99 hrs.
0
Defrosting time limitation thermostat 2
1...99 min.
30
Password of parameter level
-99 ... 999
-19