Order no.: 900312.001
V2.0
Page 32
Register table
The base address for the registers are 1000 ( = 0x03E8).
Till register number 19 the values have a precision of one decimal place, means, you have to devide the
transmitted value by 10 to get the real value.
Reg.
Nr.
Register
Address
R/W Name
Function
Range
unit
0
0x03E7
R
--1
Display
-50.0...150.0 °C
-1000.0 = error
signed
1
0x03E8
R
H11
Cold store temperature
-50.0...150.0 °C
-1000.0 = error
signed
2
0x03E9
R
H21
Evaporator temperature
-50.0...150.0 °C
-1000.0 = error
signed
3
0x03EA
R
--4
Actuating variable evaporator fan
0.0...100.0 %
signed
4
0x03EB
R/W --5
Cold store setpoint
-50.0...150.0 °C
-1000.0 = error
signed
5
0x03EC
R
H--
Condenser temperature
-50.0...150.0 °C
-1000.0 = error
signed
6
0x03ED
R
--7
Proportional value condenser fan
-100.0...100.0 %
signed
7
0x03EE
R
--8
Actuating variable condenser fan
0.0...100.0 %
signed
8
0x03EF
R/W -12
Setpoint condenser fan
-50.0...150.0 °C
-1000.0 = error
signed
9
0x03F0
R
--9
Cold store temperature via test bottle
function
-50.0...150.0 °C
-1000.0 = error
signed
10 0x03F1
R
A19
Min temperature
-50.0...150.0 °C
-1000.0 = error
signed
11 0x03F2
R
A18
Max temperature
-50.0...150.0 °C
-1000.0 = error
signed
12 0x03F3
R
H--
Temperature circuit 2
-50.0...150.0 °C
-1000.0 = error
signed
13 0x03F4
R/W -13
Setpoint circuit 2
-50.0...150.0 °C
-1000.0 = error
signed
14 0x03F5
R
t 0
Time
-50.0...150.0 °C
-1000.0 = error
signed
15 0x03F6
R
H11
Sensor F1
-50.0...150.0 °C
-1000.0 = error
signed
16 0x03F7
R
H21
Sensor F2
-50.0...150.0 °C
-1000.0 = error
signed
17 0x03F8
R
H31
Sensor F3
-50.0...150.0 °C
-1000.0 = error
signed
18 0x03F9
R
H41
Sensor F4
-50.0...150.0 °C
-1000.0 = error
signed
19 0x03FA
R
H51
Sensor F5
-50.0...150.0 °C
-1000.0 = error
signed
20 0x03FB
R
n 0
Switching cycles Relay K1 *1
0 … 999
unsigned
21 0x03FC
R
n 1
Switching cycles Relay K1 *1000
0 … 999 (*1000)
unsigned
22 0x03FD
R
n 2
Switching cycles Relay K2 *1
0 … 999
unsigned
23 0x03FE
R
n 3
Switching cycles Relay K2 *1000
0 … 999 (*1000)
unsigned
24 0x03FF
R
n 4
Switching cycles relay K3 *1
0 … 999
unsigned