10.4.1 minimum clearances
≥500
≥200
≥1000
≥50
≥500
D
00000
34
46
9
f
f
Maintain the minimum clearances to ensure trouble-free op-
eration of the appliance and facilitate maintenance work.
10.1 electrical installation
DANGER Electrocution
Carry out all electrical connection and installation work
in accordance with national and regional regulations.
DANGER Electrocution
Use a permanent connection to the power supply. Ensure
the appliance can be separated from the power supply by
an isolator that disconnects all poles with at least 3 mm
contact separation. This requirement can be met with
contactors, circuit breakers, fuses, etc.
WARNING Electrocution
The appliance contains inverters (e.g. variable speed
compressors, high efficiency circulation pumps or high
efficiency fans). In case of a fault inverters can cause DC
residual currents. If RCDs are provided, they have to be
type B AC/DC-sensitive.
A DC residual current can block type A RCDs.
f
f
Make sure that the appliance power supply is dis-
connected from the fuse board/distribution panel.
Note
The specified voltage must match the mains voltage. Ob-
serve the type plate.
Install cables with the following cross-sections in accordance with
the respective fuse rating:
Fuse/mCB
rating
assignment
Cable cross-section
C 16 A
Compressor
2.5 mm²
B 16 A
Electric emergency/
booster heater (BH)
2.5 mm²
1.5 mm² with only two live cores and
routing on a wall or in an electrical con-
duit on a wall.
B 16 A
Control unit
1.5 mm²
The electrical data is provided in the chapter "Specification / Data
table".
!
Material losses
Provide separate fuses/MCBs for the two power circuits
of the compressor and the electric emergency/booster
heater.
11. installation
11.1 transport
f
f
Transport the appliance in its packaging to protect it against
damage.
f
f
Protect the appliance against heavy impact during transport.
- If the appliance needs to be tilted during transport only do so
for a short time to one of its longitudinal sides.
The longer the appliance is tilted, the greater the distribution
of refrigerant oil in the system.
- Storage and transport at temperatures below - 20 °C and
above + 50 °C are not permissible.
To facilitate transportation you can also divide the appliance by
removing the refrigeration unit.
11.1.1 dividing the appliance
Proceed as follows:
f
f
Remove the upper packaging.
Содержание WPC 04
Страница 49: ...www stiebel eltron com WPC WPC cool 49 Installation Specification ...
Страница 61: ...www stiebel eltron com WPC WPC cool 61 Notes COP 0 1 2 3 4 5 6 7 8 5 0 5 10 15 20 1 2 3 4 D0000033166 ...
Страница 68: ...68 WPC WPC cool www stiebel eltron com Notes ...
Страница 69: ...www stiebel eltron com WPC WPC cool 69 Notes ...
Страница 70: ...70 WPC WPC cool www stiebel eltron com Notes ...