Sterling SHR150 Скачать руководство пользователя страница 9

ZP-MEC3-BX-01A 

SHR 150/200 Manual 

RD: MAY, 2004 

RL:1 

KH

 

ANGLE MOUNTING 

This heater is suitable for mounting angles with the short 
axis rotated in either direction as shown in Figure 3.   
Improper angle mounting can result in damage to the 
heater or unsafe operation. 
 

IMPORTANT:

  For either horizontal or angle mounting, 

the long axis of the heater must be level.  Use only non-
combustible mounting hardware.  In general, mounting 
angles above 25° are only used for special application of 
spot and area heating. 

VENTILATION REQUIREMENTS 

Natural or mechanical means shall be provided to 
exhaust at least 4 CFM per 1,000 BTU per hour 
input on installed heaters on Natural gas, 4.5 
CFM per 1,000 BTU per hour input on installed 
heaters on LP gas.  Exhaust openings for remov 

ing flue products shall be above the level of the 
heaters. 
When buildings are so tight that normal  
infiltration does not provide the necessary air for 
combustion, outside air must be introduced. 

IMPORTANT: 

PIPING PRACTICES

 

1.      Installation of ground pipe joint union is  
         required at the gas inlet connection to the 
         control valve on the heater.  All components 
         upstream of the control valve are field sup
         plied by the installer.  See Figure 4. 
2.      If permitted by code, an approved 18” or 24”  
         flexible connection between the heater and 
         piping is recommended. 
3.      Installation of a 6” gas line trap “Drip-Leg” is 
         required at the inlet connection to the 
         heater.  Failure to provide a drip leg could 
         result in condensation and foreign matter in 
         the valve which could cause damage. 
4. On propane-fired heaters, a main line filter 

 is recommended. 

5.     Installation of a manual shut off valve is  
        required.  Provide a 1/8 inch N.P.T. plugged 
        tap, accessible for test gauge connection, 
        immediately upstream of the gas supply 
        connection to the heater.  It may be part of 
        the shut off valve as shown in Figure 4. 
6.     Piping joint compounds must be resistant to 
        the action of liquefied petroleum gases. 
7. All piping must be installed according to  
       local codes. 
8.     To insure proper performance and full input 
        capacity, the gas supply line leading to the 
        heater from the main supply should be of an 
        adequate size.  Check your local plumbing 
        codes for correct sizing for your installation. 

FIGURE  3 

FIGURE  4 

Содержание SHR150

Страница 1: ...ra tion service or maintenance can cause property damage injury or death Read the instructions thoroughly before install ing or servicing this equipment FOR YOUR SAFETY DO NOT store or use gasoline or...

Страница 2: ......

Страница 3: ...the heater Failure to do so could cause property damage bodily injury or death Rigid mounting should be used in the above application DO NOT hang heater on gas lines water lines conduit etc Hang only...

Страница 4: ...13 Please call your local heating parts supplier and or gas company for orifices in your area IMPORTANT WARNING Do Not alter the installed orifice in any manner Improper alteration could result in Ca...

Страница 5: ...are twisted together and connect the thermostat between them If a thermostat is not used connect the red wires to the positive side of the power source and the single blue wire to the negative via a...

Страница 6: ...s by wearing personal protective equipment such as gloves and safety glasses to avoid being injured by sharp metal edges in or around the heater and while cutting or drilling holes Failure to follow t...

Страница 7: ...e largest aircraft to be housed in the hangar 2 A minimum clearance of 8 feet must be maintained from the bottom of the heater in other sections of the aircraft hangars such as offices and shops 3 The...

Страница 8: ...xis Improper angle mounting can result in overheat ing of controls and combustible materials The hangers support the infra red heater and the reflectors Chain with a working load of at least 200 lbs i...

Страница 9: ...pipe joint union is required at the gas inlet connection to the control valve on the heater All components upstream of the control valve are field sup plied by the installer See Figure 4 2 If permitte...

Страница 10: ...d pressure with a water manometer to verify proper operation of the heater A pressure regulator is an integral part of the automatic valve on all models for both Natural and LP Gas This pressure regul...

Страница 11: ...trol is powered by a 24 VAC transformer and activated when the temperature control requests for heat When the control is activated by the temperature control s request for heat control performs a safe...

Страница 12: ...OR 24 VAC ACROSS VALVES AND VALVES TERMI NALS ON CONTROL IF NO VOLTAGE REPLACE CONTROL SPARK IGNITERS MAY BE OUT OF POSITION CHECK ELEC TRICAL CONNECTIONS BETWEEN CONTROL GAS VALVES IF OKAY REPLACE GA...

Страница 13: ...ide of the ceramic This can be very easily removed by dusting the ceramic face and the air inlet with a blast of low pressure air a maximum of 20 psi Occasionally pilots or the burners refuse to funct...

Страница 14: ...448 G1 12 Gasket Fiberfraux 49929 G1 49929 G1 49229 G1 49229 G1 13 Ceramic Tile 52138 G2 52138 G2 52138 G2 52138 G2 14 Central Tile Divider 51878 G1 51878 G1 51878 G1 51878 G1 15 Tile Retainer 51295 G...

Страница 15: ...DARD ORIFICE DMS FOR USE AT ALTITUDES ABOVE FEET 2000 3000 4000 5000 6000 7000 8000 SHR150L 27 28 28 29 29 29 30 30 PART NO 49955 G18 49955 42 49955 42 49955 G11 49955 G11 49955 G11 49955 G1 49955 G1...

Страница 16: ...r 5 All service and warranty claims must have the product model and serial number on the Returned Material Tag Under no circumstances should anyone ex cept a professional gas heating equipment service...

Страница 17: ...perature or open flame excessive thermal shock physical damage impact or abrasion alterna tions by unauthorized service operation contrary to Sterling s instructions or if the serial number has been...

Отзывы: