
ZP-MEC3-BX-01A
SHR 150/200 Manual
RD: MAY, 2004
RL:1
KH
5
IMPORTANT
: In certain installations, clearances
in Table A & Figure 1 may not be adequate to
keep temperatures below 160°F. In these instal-
lations, it is the installer’s responsibility to insure
that single or multi-heater placement be such that
continuous operation of the heater or heaters will
not cause combustible materials or materials in
storage to attain a temperature of excess of 160°
F.
NOTE
: When heaters are installed in proximity to
temperature-sensitive material (for example, vinyl
faced insulation), it is the installer’s responsibility
to insure that the surface temperature does not
exceed the allowable temperature of that mate-
rial. In these installations, minimum clearances
noted in Table A on page 4 are to be increased
by the necessary amount.
Under no circumstances should this heater be
installed in a combustible atmosphere or in a
location where the heater controls can be subject
to ambient temperatures in excess of 150°F.
INSTALLATION IN AIRCRAFT HANGARS
This heater is suitable for use in aircraft hangars
when installed in accordance with the following
standard: NFPA No. 409 (latest edition).
1. A clearance of 10 feet must be maintained
from the bottom of the heater to the highest
surface of the largest aircraft to be housed
in the hangar.
2. A minimum clearance of 8 feet must be
maintained from the bottom of the heater in
other sections of the aircraft hangars, such
as offices and shops.
3. The heater must be located so that it will be
protected from damage by aircraft and other
objects, such as cranes and movable scaf
folding.
4. The heater must be installed where it will be
accessible for serving and adjustment.
INSTALLATION IN COMMERCIAL GARAGES
This heater is suitable for use in commercial
garages when installed in accordance with ANSI/
NFPA No. 88B 1985 (latest edition), which states
clearances to combustible construction or
material in storage, from heater and vent, must
conform to standard NFPA No. 54 (ANSI Z223.1
latest edition), in U.S.A. and in Canada CSA
B149.1-00.
American National Standard Institute (ANSI)
Z223.1 (latest edition) states “overhead heaters
shall be installed at least (8) feet above the floor.”
In addition, they shall be located high enough to
maintain the minimum distance to combustibles,
as shown on the heater rating plate, between the
heater and any vehicles parked below the heater.
INSTALLATION OTHER THAN SPACE HEATING
Use for processing applications voids the
warranty and C.S.A. certification. Any additional
changes, or conversions required in order for the
heater to satisfactorily meet the heater needs
must be made by a Sterling distributor, or other
qualified agency, using factory specified and ap-
proved parts.
HEATER INSTALLATION CON’T
Содержание SHR150
Страница 2: ......