SECTION V - UNIT START-UP

Close or replace all doors and service panels.

Turn main disconnect switch off. Verify the incoming line
voltage matches the unit nameplate rating. If the voltage is
over ±10% of nameplate rating or phase voltage unbalance
is over 2%, notify the contractor or power company.

Turn Heat OFF/ON switch to the OFF position. Turn main
disconnect switch on. Turn Fan OFF/ON switch to the
ON position. Damper opens. Blower fan turns on.

Turn Fan OFF/ON switch to OFF position and check sup-
ply blower for proper rotation.

NOTE: To change rotation of the blower, simply
interchange any two (2) of the line leads of the
motor starter for three (3) phase motors. Refer to
motor nameplate for reversing single (1) phase
motors.

Turn Fan OFF/ON switch to the ON position. Check for
proper blower rpm. Check that all motor amp draws do
not exceed nameplate ratings, and the overload relay is set
to the motor nameplate amperage.

Check dampers for proper operation. Be sure they operate
freely, and the linkage does not bind.

Make sure all manual gas shut-off valves are in the closed
position.

Turn Heat OFF/ON switch to the ON position. Blower
fan will run.

Turn Fan and Heat OFF/ON switches to OFF position.

Setting Burner

NOTE: To adjust gas pressure on supply lines where
a regulator has been installed (to reduce the inlet
pressure to 1/2 PSIG or less), remove dust cap of main
gas regulator and turn adjusting screw clockwise to
increase pressure, or counter-clockwise to decrease
pressure.

Set all thermostats to call for heat. Set inlet ductstat (if
applicable) above outside air temperature.

Connect a DC microammeter between the SENSE terminal
and the flame rod sensing wire.

Turn Fan and Heat OFF/ON switches to ON position.

Open inlet manual gas shut-off valve slowly. Reset high and
(if applicable) low gas pressure switches. Check main gas
line for leaks using soap solution.

Unit will run for 5 seconds before ignition trial.

NOTE: 3 OR 4 TRIALS MAY BE NEEDED TO
PURGE AIR FROM GAS LINE.

United Technologies Electronic Controls Spark Ignitor

Watch microammeter carefully. The reading should be at
least 5.0 microamps. If the reading is too low, slowly turn
the low-fire adjustment on the modulating valve in or out
until satisfactory readings are obtained. When adjusting 
low fire, there should be a continuous flame along the
entire burner length without any blowout spots.

Refer to Maxitrol Valve Adjustment instructions 
in Section IX for setting high and low fire gas 
pressure settings.

When the flame is adjusted, shut the unit off by turning the
Fan and Heat switches to OFF.

Setting Main Flame

Install manometer at test port on the last tee of the burner
manifold or modulating valve.

Slowly

open all manual gas shut-off valves.

Restart unit. After main gas valves open and burner lights
check gas lines for leaks.

Adjust high gas pressure reading (from manometer) to
match firing rate shown on unit nameplate.

Adjust the high and low fire setting according to the
Maxitrol Valve Adjustment instructions in Section IX. The
high fire setting 

must not

exceed the pressure stated on

the rating plate.

When adjusting low fire, there should be a continuous flame
along the entire burner length without any blow out spots.

Main flame is now set. Recheck the microamp signal on the
ignition control throughout the full burner input range. Re-
check low fire setting. Cycle unit 2 or 3 times to insure
good ignition.

Safety Controls Check

A. High Temperature Limit and Firestats – These limit

controls are not adjustable and are checked by the 
factory. Reset the red button(s) to be sure they are 
ready for operation. Contact the factory if these switch-
es fail to reset.

B. Ignition Control - Operate unit in Heat mode. After

flame has been established, close last manual gas valve
before main burner.The ignition control must trip out
within 15 seconds. Reset the ignition control by turning
the HEAT switch to the OFF position.

Содержание SDRIOM-2

Страница 1: ...age injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment WARNING Install operate and maintain unit in accordance with m...

Страница 2: ...allow Optional inlet hoods or other large accessories are assembled and shipped mounted and wired whenever possible within limitations of shipping and handling Any optional accessories shipped separa...

Страница 3: ...sed to the weather Rotate fan monthly B Locating the Unit Prior to locating the unit authorities having jurisdiction should be consulted before installations are made Approval permits should be checke...

Страница 4: ...be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1 2 PSI...

Страница 5: ...belts for tightness tension and alignment Do not over tighten belts 6 Check set screws on all bearings pulleys and fans for tightness 7 Check voltage supplied to disconnect switch The maximum voltage...

Страница 6: ...using soap solution Unit will run for 5 seconds before ignition trial NOTE 3 OR 4 TRIALS MAY BE NEEDED TO PURGE AIR FROM GAS LINE UnitedTechnologies Electronic Controls Spark Ignitor Watch microammete...

Страница 7: ...replaced When checking operation of air pressure switches on systems without pilot the heat switch will have to be turned off approximately five seconds to reset the igni tion control E Temperature C...

Страница 8: ...oltage at ignition control C Burner does not light after 5 sec onds pre purge of flame safeguard relay and there is voltage at igni tion control 1 Check power source 2 Check and replace 3 Close or con...

Страница 9: ...valves If gas pressure matches unit rating plate and valve does not open replace gas valve or actuator 10 Make sure spark rod is producing a sufficient spark to light off burner make sure porcelain i...

Страница 10: ...10 SECTION VII TROUBLESHOOTING P 001004 P 001003...

Страница 11: ...d modulating voltages are still not obtained amplifier may be assumed faulty Replace 1 Replace modulator head if not approximately 45 55 ohms for M611Valve and 60 80 ohms for MR212 Valve 2 Clean or re...

Страница 12: ...let to modulating valve using a manometer with unit operating at full fire Pressure should be equal to the sum of outlet pres sure setting plus pressure drop of the valve 2 Read manifold pressure usin...

Страница 13: ...between amplifier and modulator valve 1 Override Temperature setting is too low 2 Burner capacity may be insufficient 1 Faulty automatic control valve 2 Open wire to automatic valve 13 Symptom Possib...

Страница 14: ...inals 4 5 Set T244 or TD244 to max imum setting Measure resistance across wires Meter should read 6000 ohms 1000 T244 If TS244 TD244 are used meter should read 4500 ohms 1000 TS244 and 2100 ohms 150 T...

Страница 15: ...cessary 1 Move TS144 to location where average temperature can be sensed 2 If proper temperatures are not observed refer to Discharge Air Temperature calibration procedures 1 Clean replace valve and o...

Страница 16: ...h pressure regulator to match the appliance rating a Remove the pressure regulator adjustment cap b Using a screwdriver turn the inner adjustment screw for HI pressure clockwise to increase or counter...

Страница 17: ...sure that no com bustible or hazardous material has been stored within the clearances as shown on the unit name plate 3 Quarterly a Complete the monthly maintenance schedule b Check the belt tension f...

Страница 18: ...casing of the motor Add a small amount of a clean good grade ball bearing grease such as Exxon Polyrex EM or equal with a low pressure grease gun Run the motor five minutes before removing the grease...

Страница 19: ...inspection covers some filter racks and some outdoor air dampers Inspect gaskets periodically and repair or replace as required G Heater 1 At least a yearly inspection is recommended for heating insta...

Страница 20: ...e solution 5 Inspect the support means to be sure that everything is firmly anchored in place SECTION IX MAXON NP I AIRLO BURNERS Inspection and Maintenance of Gas Ports Conduct initial inspection wit...

Страница 21: ...ontinuous low fire 2 Remove cap B and loosen lock screw C Turn D to desired low fire adjustment Clockwise rotation reduces minimum flow rate 3 Tighten screw C replace cap B and reconnect wire to ampli...

Страница 22: ...m can be isolated to the electronics and this may once again be reviewed in the check list After test remove the test resistor and reconnect the Discharge Air Sensor to terminals 3 and 4 If Remote Tem...

Страница 23: ...lem is identified with the space temperature sensing and or temperature selecting components and circuits See Troubleshooting Guide If proper delivered air temperatures are not observed check calibrat...

Страница 24: ...cient ventilation air which results in inadequate dilution of combustion products gen erated by the heater may create hazardous concentrations of carbon monoxide nitrogen dioxide and other combus tion...

Отзывы: