16

L. Incorrect Space

Temperature 

1. Incorrect maximum

discharge air
temperature setting
(A1044).

2. Incorrect minimum

discharge air 
temperature 
setting (A1044).

3. Insufficient burner

capacity.

4. Incorrect space

temperature
calibration.

1. Check to see if heater is

delivering air at maximum
discharge air setting.

2. Check to see if heater is

delivering air at minimum
discharge air setting.

3. Check to see if heater is

operating at high fire.

4. Place thermometer next

to T244  or TS244. Compare
space temperature reading
with T244  or TD244  dial
setting.

1. If desired temperature is

not reached, increase
maximum discharge air
temperature setting.

2. If desired space temperature

is not reached, decrease
minimum discharge air
temperature setting.

3. If desired space temperature

is not reached with heater at
high fire, it may be undersized.

4. Consult factory. If tempera-

ture reading is incorrect,
check items L1, L2 & L3, then
recalibrate if necessary.

Control circuits external to Series 44 can cause burner malfunction. Always check manual valve to be

certain gas is on, and check limit controls for normal operation.

Honeywell Two  Stage Valve

Two-stage models require that you check and adjust both
high and low pressure regulator settings.Two-stage appli-
ance operating sequences vary. Consult the appliance man-
ufacturer instructions for the specific operating sequence
and regulator adjustment procedure for the appliance in
which the control is installed.
1. Set appliance to operate on high.
2. Carefully check the main burner lightoff. Make sure that

the main burner lights smoothly and that all ports
remain lit.

3. Check the full rate (high) manifold pressure listed on

the appliance nameplate for high pressure.The gas con-
trol full rate outlet pressure should match this rating.

4. With main burner operating, check the gas control flow

rate using the meter clocking method or check pres-
sure using a manometer connected to the outlet pres-
sure tap on the gas control.

5. If necessary, adjust the high pressure regulator to match

the appliance rating.

a. Remove the pressure regulator adjustment cap.
b. Using a screwdriver, turn the inner adjustment screw

for HI pressure clockwise               to increase or
counterclockwise              to decrease the gas pres-
sure to the burner.

6. After high pressure has been checked, check low pres-

sure regulation.Two-stage appliance operating
sequences vary. Consult the appliance manufacturers
instructions for the specific operating sequence and reg-
ulator adjustment procedure for the appliance in which
the control is installed and for instructions on how to
prevent the control from moving to high stage while
checking the low pressure regulator setting.

7. Check the low rate manifold pressure listed on the

appliance nameplate. Gas control low rate outlet pres-
sure should match this rating.

8. With main burner operating, check the gas control flow

rate as before (using the meter clocking method or
check pressure using a manometer connected to the
outlet pressure tap on the control).

9. If necessary, adjust the low pressure regulator to match

the appliance rating.

a. Remove the pressure regulator adjustment cap.
b. Using a screwdriver, turn the inner adjustment screw

for LO pressure clockwise              to increase or
counterclockwise              to decrease the gas pres-
sure to the burner.

10.Once high and low pressure have been checked and 

adjusted, replace pressure regulator adjustment cap. If 
the desired outlet pressure or flow rate can not be
achieved by adjusting the gas control, check the 
control inlet pressure using a manometer at the inlet 
pressure tap of the control. Take the necessary steps to
provide proper gas pressure to the control.

Check Safety Shutdown Performance

NOTE: Read steps 1 through 7 before starting, and
compare to the safety shutdown or safety lockout
tests recommended for the intermittent pilot (IP)
ignition module.Where diffferent, use the proce-
dure recommended for the module.

WARNING: Fire or explosion hazard. Can cause
property damage, severe injury or death. Perform
the safety shutdown test any time work is done
on a gas system.

TROUBLESHOOTING GUIDE

Series 44 Room Temperature Control 

continued

Reproduced with permission from Maxitrol® Company

Содержание SDRIOM-2

Страница 1: ...age injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment WARNING Install operate and maintain unit in accordance with m...

Страница 2: ...allow Optional inlet hoods or other large accessories are assembled and shipped mounted and wired whenever possible within limitations of shipping and handling Any optional accessories shipped separa...

Страница 3: ...sed to the weather Rotate fan monthly B Locating the Unit Prior to locating the unit authorities having jurisdiction should be consulted before installations are made Approval permits should be checke...

Страница 4: ...be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1 2 PSI...

Страница 5: ...belts for tightness tension and alignment Do not over tighten belts 6 Check set screws on all bearings pulleys and fans for tightness 7 Check voltage supplied to disconnect switch The maximum voltage...

Страница 6: ...using soap solution Unit will run for 5 seconds before ignition trial NOTE 3 OR 4 TRIALS MAY BE NEEDED TO PURGE AIR FROM GAS LINE UnitedTechnologies Electronic Controls Spark Ignitor Watch microammete...

Страница 7: ...replaced When checking operation of air pressure switches on systems without pilot the heat switch will have to be turned off approximately five seconds to reset the igni tion control E Temperature C...

Страница 8: ...oltage at ignition control C Burner does not light after 5 sec onds pre purge of flame safeguard relay and there is voltage at igni tion control 1 Check power source 2 Check and replace 3 Close or con...

Страница 9: ...valves If gas pressure matches unit rating plate and valve does not open replace gas valve or actuator 10 Make sure spark rod is producing a sufficient spark to light off burner make sure porcelain i...

Страница 10: ...10 SECTION VII TROUBLESHOOTING P 001004 P 001003...

Страница 11: ...d modulating voltages are still not obtained amplifier may be assumed faulty Replace 1 Replace modulator head if not approximately 45 55 ohms for M611Valve and 60 80 ohms for MR212 Valve 2 Clean or re...

Страница 12: ...let to modulating valve using a manometer with unit operating at full fire Pressure should be equal to the sum of outlet pres sure setting plus pressure drop of the valve 2 Read manifold pressure usin...

Страница 13: ...between amplifier and modulator valve 1 Override Temperature setting is too low 2 Burner capacity may be insufficient 1 Faulty automatic control valve 2 Open wire to automatic valve 13 Symptom Possib...

Страница 14: ...inals 4 5 Set T244 or TD244 to max imum setting Measure resistance across wires Meter should read 6000 ohms 1000 T244 If TS244 TD244 are used meter should read 4500 ohms 1000 TS244 and 2100 ohms 150 T...

Страница 15: ...cessary 1 Move TS144 to location where average temperature can be sensed 2 If proper temperatures are not observed refer to Discharge Air Temperature calibration procedures 1 Clean replace valve and o...

Страница 16: ...h pressure regulator to match the appliance rating a Remove the pressure regulator adjustment cap b Using a screwdriver turn the inner adjustment screw for HI pressure clockwise to increase or counter...

Страница 17: ...sure that no com bustible or hazardous material has been stored within the clearances as shown on the unit name plate 3 Quarterly a Complete the monthly maintenance schedule b Check the belt tension f...

Страница 18: ...casing of the motor Add a small amount of a clean good grade ball bearing grease such as Exxon Polyrex EM or equal with a low pressure grease gun Run the motor five minutes before removing the grease...

Страница 19: ...inspection covers some filter racks and some outdoor air dampers Inspect gaskets periodically and repair or replace as required G Heater 1 At least a yearly inspection is recommended for heating insta...

Страница 20: ...e solution 5 Inspect the support means to be sure that everything is firmly anchored in place SECTION IX MAXON NP I AIRLO BURNERS Inspection and Maintenance of Gas Ports Conduct initial inspection wit...

Страница 21: ...ontinuous low fire 2 Remove cap B and loosen lock screw C Turn D to desired low fire adjustment Clockwise rotation reduces minimum flow rate 3 Tighten screw C replace cap B and reconnect wire to ampli...

Страница 22: ...m can be isolated to the electronics and this may once again be reviewed in the check list After test remove the test resistor and reconnect the Discharge Air Sensor to terminals 3 and 4 If Remote Tem...

Страница 23: ...lem is identified with the space temperature sensing and or temperature selecting components and circuits See Troubleshooting Guide If proper delivered air temperatures are not observed check calibrat...

Страница 24: ...cient ventilation air which results in inadequate dilution of combustion products gen erated by the heater may create hazardous concentrations of carbon monoxide nitrogen dioxide and other combus tion...

Отзывы: