Symptom

Possible Cause 

Field Test

Remedy

E.

continued

F. Incorrect 

Maximum or
Minimum 
Discharge Air
Temperature.

G. Continuous High 

Fire (Electronics 
OK).

H. Continuous High

Fire (Electronics
Problem).

I. Incorrect High Fire 

J. Continuous 

Maximum Discharge
Air Temperature.

K. Burned out

Transformer. No
Voltage to Amplifier.

3. Follow procedures outlined

in “Preliminary  Circuit
Analysis” in Section IX.

1. Compare sensed

temperature reading at
TS144 with average
discharge air temperature.

2. Follow procedures outlined

in “Preliminary  Circuit
Analysis” in Section IX.

1. Remove bottom plate and

inspect valve and seat.

2. Inspect. Plunger should

be smooth and clean and
operate freely in solenoid
sleeve.

1. Measure resistance per 

item C3.

1. Read inlet pressure at valve

using manometer with
heater operating at full fire.
Pressure should be at least
equal to the sum of: outlet
pressure setting and 
pressure drop of the valve
plus 1.0” W.C.

2. Read outlet pressure using

manometer and compare
with the pressure stated 
on the specification plate.

1. Follow procedures outlined 

in “Preliminary  Circuit
Analysis” in Section IX.

2. Measure resistance per

item E2.

3. Follow procedures outlined 

in “Preliminary  Circuit
Analysis” in Section IX.

1. Measure resistance per 

item B1.

3. If proper action is obtained,

first check item E2.
Recalibrate if necessary.

1. Move TS144 to location

where average temperature
can be sensed.

2. If proper temperatures are

not observed, refer to
Discharge Air Temperature
calibration procedures.

1. Clean, replace valve and/or 

seat if necessary.

2. Clean, or if necessary,

replace plunger

1. If readings are incorrect,

replace the TS144 or repair
wiring.

1. Increase inlet pressure if 

possible or change to larger
valve. Consult factory 
about possibility of using 
special spring to reduce 
pressure drop on selected
installations.

2. See Valve Adjustments  in

Section IX.

1. If amplifier is proven at

fault, install replacement
amplifier.

2. If reading is incorrect,

replace T244,
TS244/TD244 or repair
wiring.

3. If proper action is obtained,

first check item J2.
Recalibrate if necessary.

1. If proper resistances are 

not observed, replace 
modulator head or repair
wiring.

Control circuits external to Series 44 can cause burner malfunction. Always check manual valve to be

certain gas is on, and check limit controls for normal operation.

3. Incorrect space 

temperature calibration.

1. Improper TS144 

location.

2. Incorrect discharge

air temperature 
calibrations.

1. Foreign material

holding valve open.

2. Plunger jammed.

1. Open circuit in TS144.

1. Inlet pressure too low.

2. Incorrect outlet

pressure adjustment.

1. Faulty amplifier.

2. Open circuit in T244

or TS244/TD244.

3. Incorrect space

temperature calibration.

1. Short in modulator coil

circuit.

TROUBLESHOOTING GUIDE

Series 44 Room Temperature Control 

continued 

Reproduced with permission from Maxitrol® Company

Содержание SDRIOM-2

Страница 1: ...age injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment WARNING Install operate and maintain unit in accordance with m...

Страница 2: ...allow Optional inlet hoods or other large accessories are assembled and shipped mounted and wired whenever possible within limitations of shipping and handling Any optional accessories shipped separa...

Страница 3: ...sed to the weather Rotate fan monthly B Locating the Unit Prior to locating the unit authorities having jurisdiction should be consulted before installations are made Approval permits should be checke...

Страница 4: ...be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1 2 PSI...

Страница 5: ...belts for tightness tension and alignment Do not over tighten belts 6 Check set screws on all bearings pulleys and fans for tightness 7 Check voltage supplied to disconnect switch The maximum voltage...

Страница 6: ...using soap solution Unit will run for 5 seconds before ignition trial NOTE 3 OR 4 TRIALS MAY BE NEEDED TO PURGE AIR FROM GAS LINE UnitedTechnologies Electronic Controls Spark Ignitor Watch microammete...

Страница 7: ...replaced When checking operation of air pressure switches on systems without pilot the heat switch will have to be turned off approximately five seconds to reset the igni tion control E Temperature C...

Страница 8: ...oltage at ignition control C Burner does not light after 5 sec onds pre purge of flame safeguard relay and there is voltage at igni tion control 1 Check power source 2 Check and replace 3 Close or con...

Страница 9: ...valves If gas pressure matches unit rating plate and valve does not open replace gas valve or actuator 10 Make sure spark rod is producing a sufficient spark to light off burner make sure porcelain i...

Страница 10: ...10 SECTION VII TROUBLESHOOTING P 001004 P 001003...

Страница 11: ...d modulating voltages are still not obtained amplifier may be assumed faulty Replace 1 Replace modulator head if not approximately 45 55 ohms for M611Valve and 60 80 ohms for MR212 Valve 2 Clean or re...

Страница 12: ...let to modulating valve using a manometer with unit operating at full fire Pressure should be equal to the sum of outlet pres sure setting plus pressure drop of the valve 2 Read manifold pressure usin...

Страница 13: ...between amplifier and modulator valve 1 Override Temperature setting is too low 2 Burner capacity may be insufficient 1 Faulty automatic control valve 2 Open wire to automatic valve 13 Symptom Possib...

Страница 14: ...inals 4 5 Set T244 or TD244 to max imum setting Measure resistance across wires Meter should read 6000 ohms 1000 T244 If TS244 TD244 are used meter should read 4500 ohms 1000 TS244 and 2100 ohms 150 T...

Страница 15: ...cessary 1 Move TS144 to location where average temperature can be sensed 2 If proper temperatures are not observed refer to Discharge Air Temperature calibration procedures 1 Clean replace valve and o...

Страница 16: ...h pressure regulator to match the appliance rating a Remove the pressure regulator adjustment cap b Using a screwdriver turn the inner adjustment screw for HI pressure clockwise to increase or counter...

Страница 17: ...sure that no com bustible or hazardous material has been stored within the clearances as shown on the unit name plate 3 Quarterly a Complete the monthly maintenance schedule b Check the belt tension f...

Страница 18: ...casing of the motor Add a small amount of a clean good grade ball bearing grease such as Exxon Polyrex EM or equal with a low pressure grease gun Run the motor five minutes before removing the grease...

Страница 19: ...inspection covers some filter racks and some outdoor air dampers Inspect gaskets periodically and repair or replace as required G Heater 1 At least a yearly inspection is recommended for heating insta...

Страница 20: ...e solution 5 Inspect the support means to be sure that everything is firmly anchored in place SECTION IX MAXON NP I AIRLO BURNERS Inspection and Maintenance of Gas Ports Conduct initial inspection wit...

Страница 21: ...ontinuous low fire 2 Remove cap B and loosen lock screw C Turn D to desired low fire adjustment Clockwise rotation reduces minimum flow rate 3 Tighten screw C replace cap B and reconnect wire to ampli...

Страница 22: ...m can be isolated to the electronics and this may once again be reviewed in the check list After test remove the test resistor and reconnect the Discharge Air Sensor to terminals 3 and 4 If Remote Tem...

Страница 23: ...lem is identified with the space temperature sensing and or temperature selecting components and circuits See Troubleshooting Guide If proper delivered air temperatures are not observed check calibrat...

Страница 24: ...cient ventilation air which results in inadequate dilution of combustion products gen erated by the heater may create hazardous concentrations of carbon monoxide nitrogen dioxide and other combus tion...