Sterling SDRIOM-2 Скачать руководство пользователя страница 11

1. Modulating valve 

improperly installed (or 
see Symptom “L”).

1. Short circuit or no 

voltage to the amplifier.

2. Open circuit in TD114

Remote Temperature
Selector circuit or wiring.

3. Short circuit in TS114

Discharge Air  Sensor 
circuit of wiring.

4. Faulty amplifier.

1. Short circuit or open 

circuit in Modulator 
Coil.

2. Plunger missing, jammed,

or improperly installed.

1. Incorrect by-pass 

metering valve 
adjustment.

2. Excessive negative 

burner pressure.

11

Symptom

Possible Cause 

Field Test

Remedy

A. No Gas Flow

B. Continuous Low 

Fire (Electronics
Problem)

C. Continuous Low 

Fire (Electronics
OK).

D. Incorrect Minimum

Fire Erratic or
Pulsating Flame 

1. Arrow on side of valve

should point in direction 
of gas flow.

1. Check for 24V AC at 

amplifier terminals 7 & 8.

2. Inspect for loose or 

broken wires between
amplifier terminals 1 & 2
and TD114 terminals 1 & 3.

3. Connect test resistor as

described in Preliminary
Circuit Analysis in Section
IX. Follow procedures 
outlined.

4. Check items B1-3.

1. Measure resistance across

modulator terminals with
connecting wires detached.

2. Inspect. Plunger should be

installed to operate freely in
solenoid sleeve.

1. See valve adjustments in

Section IX.

2. Close main gas supply and

measure manifold pressure
with blower operating.
Reading should be less than
1.5” W.C. negative  pressure.

1. Install properly.

1. Prove the power source.

2. Tighten connections or

replace wiring.

3. If modulating voltages are 

obtained, check TS114 
circuit for shorts. Replace
TS114 if necessary.

4. If items B1-3 check out, and

modulating voltages are still
not obtained, amplifier may 
be assumed faulty. Replace.

1. Replace modulator head if 

not approximately 45-55
ohms for M611 Valve and 
60-80 ohms for MR212 Valve.

2. Clean or replace plunger if

necessary.

1. Adjust to proper minimum

fire.

2. If reading is greater than 1.5”

negative pressure, check for
clogged filters or other inlet
air restrictions. Consult 
factory for other solutions.

United Technologies  Electronics  Controls
Operation of the Series 1016-400 Direct Spark
Ignition Control

On a call for heat a five second pre-purge is initiated.
Upon completion of the pre-purge, the gas valve and 60
Hz spark are energized. When flame is detected, the con-
trol enters the steady state heating condition. Steady state
heating will continue until the call for heat is satisfied.

If ignition is not achieved within 15 seconds, the control
shuts off the gas and locks out

.

If the trial for ignition has

been accomplished without ignition, the control shuts off 

all outputs and enters lockout. Reset is accomplished by
cycling the power off for a minimum of 5 seconds.
If flame is lost once it has been established, the control will
shut off the gas valve within 0.8 seconds and locks out.

If flame is sensed during a purge period when no flame
should be present, the control will remain in purge with
the gas valve off until the false flame disappears.
If the gas valve is found to be powered when it should be
off, or not powered when it should be on, the control will
enter lockout with all outputs off. Reset is accomplished
by cycling the power off for a minimum of 5 seconds.

TROUBLESHOOTING GUIDE

Series 14 Discharge Temperature Control  

Reproduced with permission from Maxitrol® Company

Содержание SDRIOM-2

Страница 1: ...age injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment WARNING Install operate and maintain unit in accordance with m...

Страница 2: ...allow Optional inlet hoods or other large accessories are assembled and shipped mounted and wired whenever possible within limitations of shipping and handling Any optional accessories shipped separa...

Страница 3: ...sed to the weather Rotate fan monthly B Locating the Unit Prior to locating the unit authorities having jurisdiction should be consulted before installations are made Approval permits should be checke...

Страница 4: ...be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1 2 PSI...

Страница 5: ...belts for tightness tension and alignment Do not over tighten belts 6 Check set screws on all bearings pulleys and fans for tightness 7 Check voltage supplied to disconnect switch The maximum voltage...

Страница 6: ...using soap solution Unit will run for 5 seconds before ignition trial NOTE 3 OR 4 TRIALS MAY BE NEEDED TO PURGE AIR FROM GAS LINE UnitedTechnologies Electronic Controls Spark Ignitor Watch microammete...

Страница 7: ...replaced When checking operation of air pressure switches on systems without pilot the heat switch will have to be turned off approximately five seconds to reset the igni tion control E Temperature C...

Страница 8: ...oltage at ignition control C Burner does not light after 5 sec onds pre purge of flame safeguard relay and there is voltage at igni tion control 1 Check power source 2 Check and replace 3 Close or con...

Страница 9: ...valves If gas pressure matches unit rating plate and valve does not open replace gas valve or actuator 10 Make sure spark rod is producing a sufficient spark to light off burner make sure porcelain i...

Страница 10: ...10 SECTION VII TROUBLESHOOTING P 001004 P 001003...

Страница 11: ...d modulating voltages are still not obtained amplifier may be assumed faulty Replace 1 Replace modulator head if not approximately 45 55 ohms for M611Valve and 60 80 ohms for MR212 Valve 2 Clean or re...

Страница 12: ...let to modulating valve using a manometer with unit operating at full fire Pressure should be equal to the sum of outlet pres sure setting plus pressure drop of the valve 2 Read manifold pressure usin...

Страница 13: ...between amplifier and modulator valve 1 Override Temperature setting is too low 2 Burner capacity may be insufficient 1 Faulty automatic control valve 2 Open wire to automatic valve 13 Symptom Possib...

Страница 14: ...inals 4 5 Set T244 or TD244 to max imum setting Measure resistance across wires Meter should read 6000 ohms 1000 T244 If TS244 TD244 are used meter should read 4500 ohms 1000 TS244 and 2100 ohms 150 T...

Страница 15: ...cessary 1 Move TS144 to location where average temperature can be sensed 2 If proper temperatures are not observed refer to Discharge Air Temperature calibration procedures 1 Clean replace valve and o...

Страница 16: ...h pressure regulator to match the appliance rating a Remove the pressure regulator adjustment cap b Using a screwdriver turn the inner adjustment screw for HI pressure clockwise to increase or counter...

Страница 17: ...sure that no com bustible or hazardous material has been stored within the clearances as shown on the unit name plate 3 Quarterly a Complete the monthly maintenance schedule b Check the belt tension f...

Страница 18: ...casing of the motor Add a small amount of a clean good grade ball bearing grease such as Exxon Polyrex EM or equal with a low pressure grease gun Run the motor five minutes before removing the grease...

Страница 19: ...inspection covers some filter racks and some outdoor air dampers Inspect gaskets periodically and repair or replace as required G Heater 1 At least a yearly inspection is recommended for heating insta...

Страница 20: ...e solution 5 Inspect the support means to be sure that everything is firmly anchored in place SECTION IX MAXON NP I AIRLO BURNERS Inspection and Maintenance of Gas Ports Conduct initial inspection wit...

Страница 21: ...ontinuous low fire 2 Remove cap B and loosen lock screw C Turn D to desired low fire adjustment Clockwise rotation reduces minimum flow rate 3 Tighten screw C replace cap B and reconnect wire to ampli...

Страница 22: ...m can be isolated to the electronics and this may once again be reviewed in the check list After test remove the test resistor and reconnect the Discharge Air Sensor to terminals 3 and 4 If Remote Tem...

Страница 23: ...lem is identified with the space temperature sensing and or temperature selecting components and circuits See Troubleshooting Guide If proper delivered air temperatures are not observed check calibrat...

Страница 24: ...cient ventilation air which results in inadequate dilution of combustion products gen erated by the heater may create hazardous concentrations of carbon monoxide nitrogen dioxide and other combus tion...