PRELIMINARY CIRCUIT ANALYSIS - SYSTEM 14

For ease in troubleshooting, it is advisable to wire the 
system as follows (this differs from the normal connection).
The Discharge Air Sensor is disconnected and replaced
with a 10,000 ohm,1/2 watt test resistor (terminals 3 and
4). If inlet air sensor is being used, disconnect and replace
with a jumper. On units where the Remote Temperature
Selector is located a considerable distance from the heater,
it may be advantageous to connect the selector at the
heater location.

Connect a DC volt meter (capable of reading 0-24V DC)
on the Modulator or Modulator-Regulator Valve terminals.
Set the temperature to the minimum dial setting. The DC
voltage should read 0 volts. The DC voltage should 
gradually increase to at least 20 volts as you slowly rotate
the dial to the maximum dial setting. If these voltages are
obtained, the valve function can now be checked out.

The operation of the valve with regard to voltage is as 
follows: from 0 volts to approximately 5 volts, the 
modulating valve should be on bypass flow with the heater
operating on low or minimum fire. From approximately 
5 volts to 15 volts DC, the valve should be performing its
modulating function and the heater should be firing at a
modulated flow rate between low and high fire, depending
on the voltage. Above approximately 15 volts DC, the
valve should be delivering full flow to the heater and the
unit should be on full fire. If the DC voltage is obtained
on the valve terminals, but the heater does not respond as
described, the problem can be isolated to the valve itself
or to the gas control manifold of the heater.

In the event proper voltages are obtained and the valve
responds correctly to these DC voltages, the problem
could well be in the wiring leading to the Discharge Air
Sensor itself. This should also be reviewed in the check
list.

If the proper voltages are not obtained when wired as
instructed, the problem can be isolated to the electronics
and this may once again be reviewed in the check list.
After test, remove the test resistor and reconnect the
Discharge Air Sensor to terminals 3 and 4. If Remote
Temperature Selector has been moved, return it to its 
original position.

PRELIMINARY CIRCUIT ANALYSIS - SYSTEM 44

This Preliminary Circuit Analysis will provide identification
of faulty components, improper wiring or calibration, and
other difficulties when used with the tabulated
Troubleshooting Guide.

NOTE: All voltages and resistance readings are
approximate.

Section 1

1.

Wire the system per Figure 1.

2.

Connect a DC voltmeter to amplifier terminals #6 

and #7.

3.

Turn the Test-Potentiometer to minimum resistance

(2,000 ohms). The DC voltage should read 0 volts.

4.

Turn the Test-Potentiometer slowly to maximum 

resistance (12,000 ohms). The DC voltage should 
gradually increase to at least 18 volts.

If proper voltages are observed, continue on with
Section 2.

If proper voltages are not observed, the problem is
identified with the Amplifier, the 24-volt AC power 
supply, or the circuit connected to terminals #6 and #7.

Section 2

1.

Turn power OFF. Wire system per Figure 2. Turn

power ON.

2.

Turn Test-Potentiometer to minimum resistance.

Voltage should be 0 volts.

3.

Turn Test-Potentiometer slowly to maximum resistance.

The DC voltage should gradually increase to at least 
18 volts.

If proper voltages are observed in both Section 1 and
2, the amplifier is satisfactory.

If proper voltages are not observed, continue testing 
to identify the difficulty. Faults may be identified with
the amplifier, the 24V power supply, or the circuit 
connected to terminals #6 and #7.

Section 3

1.

Observe burner flames and/or burner pressure as 

Test- Potentiometer is turned through full range.

NOTE: From 0-5 volts, heater should be at bypass
or low; 5-15 volts, heater should respond with vari-
ous input rates; beyond 15 volts, heater is at maxi-
mum input.

If proper operation is observed, continue procedure to
check operation of sensing and selecting components.
If proper operation is not observed, see Trouble-shoot-
ing Guide to test M and MR valves and connecting
wiring.

Содержание SDRIOM-2

Страница 1: ...age injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment WARNING Install operate and maintain unit in accordance with m...

Страница 2: ...allow Optional inlet hoods or other large accessories are assembled and shipped mounted and wired whenever possible within limitations of shipping and handling Any optional accessories shipped separa...

Страница 3: ...sed to the weather Rotate fan monthly B Locating the Unit Prior to locating the unit authorities having jurisdiction should be consulted before installations are made Approval permits should be checke...

Страница 4: ...be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1 2 PSI...

Страница 5: ...belts for tightness tension and alignment Do not over tighten belts 6 Check set screws on all bearings pulleys and fans for tightness 7 Check voltage supplied to disconnect switch The maximum voltage...

Страница 6: ...using soap solution Unit will run for 5 seconds before ignition trial NOTE 3 OR 4 TRIALS MAY BE NEEDED TO PURGE AIR FROM GAS LINE UnitedTechnologies Electronic Controls Spark Ignitor Watch microammete...

Страница 7: ...replaced When checking operation of air pressure switches on systems without pilot the heat switch will have to be turned off approximately five seconds to reset the igni tion control E Temperature C...

Страница 8: ...oltage at ignition control C Burner does not light after 5 sec onds pre purge of flame safeguard relay and there is voltage at igni tion control 1 Check power source 2 Check and replace 3 Close or con...

Страница 9: ...valves If gas pressure matches unit rating plate and valve does not open replace gas valve or actuator 10 Make sure spark rod is producing a sufficient spark to light off burner make sure porcelain i...

Страница 10: ...10 SECTION VII TROUBLESHOOTING P 001004 P 001003...

Страница 11: ...d modulating voltages are still not obtained amplifier may be assumed faulty Replace 1 Replace modulator head if not approximately 45 55 ohms for M611Valve and 60 80 ohms for MR212 Valve 2 Clean or re...

Страница 12: ...let to modulating valve using a manometer with unit operating at full fire Pressure should be equal to the sum of outlet pres sure setting plus pressure drop of the valve 2 Read manifold pressure usin...

Страница 13: ...between amplifier and modulator valve 1 Override Temperature setting is too low 2 Burner capacity may be insufficient 1 Faulty automatic control valve 2 Open wire to automatic valve 13 Symptom Possib...

Страница 14: ...inals 4 5 Set T244 or TD244 to max imum setting Measure resistance across wires Meter should read 6000 ohms 1000 T244 If TS244 TD244 are used meter should read 4500 ohms 1000 TS244 and 2100 ohms 150 T...

Страница 15: ...cessary 1 Move TS144 to location where average temperature can be sensed 2 If proper temperatures are not observed refer to Discharge Air Temperature calibration procedures 1 Clean replace valve and o...

Страница 16: ...h pressure regulator to match the appliance rating a Remove the pressure regulator adjustment cap b Using a screwdriver turn the inner adjustment screw for HI pressure clockwise to increase or counter...

Страница 17: ...sure that no com bustible or hazardous material has been stored within the clearances as shown on the unit name plate 3 Quarterly a Complete the monthly maintenance schedule b Check the belt tension f...

Страница 18: ...casing of the motor Add a small amount of a clean good grade ball bearing grease such as Exxon Polyrex EM or equal with a low pressure grease gun Run the motor five minutes before removing the grease...

Страница 19: ...inspection covers some filter racks and some outdoor air dampers Inspect gaskets periodically and repair or replace as required G Heater 1 At least a yearly inspection is recommended for heating insta...

Страница 20: ...e solution 5 Inspect the support means to be sure that everything is firmly anchored in place SECTION IX MAXON NP I AIRLO BURNERS Inspection and Maintenance of Gas Ports Conduct initial inspection wit...

Страница 21: ...ontinuous low fire 2 Remove cap B and loosen lock screw C Turn D to desired low fire adjustment Clockwise rotation reduces minimum flow rate 3 Tighten screw C replace cap B and reconnect wire to ampli...

Страница 22: ...m can be isolated to the electronics and this may once again be reviewed in the check list After test remove the test resistor and reconnect the Discharge Air Sensor to terminals 3 and 4 If Remote Tem...

Страница 23: ...lem is identified with the space temperature sensing and or temperature selecting components and circuits See Troubleshooting Guide If proper delivered air temperatures are not observed check calibrat...

Страница 24: ...cient ventilation air which results in inadequate dilution of combustion products gen erated by the heater may create hazardous concentrations of carbon monoxide nitrogen dioxide and other combus tion...

Отзывы: