36
742.114 | 14.50
EN
Min. solid fuel boiler temperature
85 °F
200 °F
125 °F
Control target for solid fuel boiler
temperature (Speed control =
on
)
32 °F
200 °F
140 °F
1)
Notice
Standard pump: Set
AC
!
High-efficiency pump: Set
HE
!
2)
Notice
External consumer (e.g. 115 V relay): Set
AC
pump type and set the speed control to
oFF
!
10.3.5 Quick charge
Uses a higher loading temperature to load the upper region of the storage
tank more quickly in order to provide early prevention of back-up heating
by the conventional heating system. To do this, the loading strategy of the
first-priority storage tank is changed from differential loading to absolute
temperature loading as soon as the temperature in the upper tank region
drops below T
on
*)
. At the same time, an attempt is made to achieve a
higher temperature in the storage tank by using the speed control.
*)
To retain the proven quick charge functionality, when T
on
is changed, the value
of T
off
is changed in parallel.
Note
To use the
quick charge
function, the speed control must be switched on;
more information on this is provided in Section 11, p. 45 (P18, P19).
Display
Characteristic
min.
max.
Factory
setting
Activation
on
,
oFF
oFF
Sensor input for upper storage tank
temperature
1 ... 5
–
Switch-on temperature T
on
32 °F
185 °F
125 °F
Switch-off temperature T
off
T
on
+ 4 F
T
on
+ 20 F
130 °F