10.3.4 Solid fuel boiler
Controls a pump in order to heat a storage tank using a solid fuel boiler.
The pump is switched on when all of the following conditions are satis-
fied at the same time:
• The temperature difference between the solid fuel boiler and the
storage tank exceeds
T
diff on
.
• The solid fuel boiler temperature lies above the
min. solid fuel boiler
temperature
.
• The storage tank temperature lies below the
max. storage tank
temperature
.
The pump is switched off when one of the following conditions is satisfied:
• The temperature difference between the solid fuel boiler and the
storage tank drops below
T
diff off
.
• The solid fuel boiler temperature drops below the
min. solid fuel
boiler temperature
.
• The storage tank temperature reaches the
max. storage tank tem-
perature.
Speed control of the pump can be activated as required. The loading
strategy of the speed control system attempts to regulate the tempera-
ture of the solid fuel boiler to match the control target that has been set.
The control target should be at least 20 F above the minimum tempera-
ture of the solid fuel boiler.
Display
Characteristic
min.
max.
Factory
setting
Activation
on
,
oFF
oFF
Output (pump)
free output
R1
/
R2
/
R
S
–
Pump type (
R1
,
R2
only)
AC
,
HE
1) 2)
AC
Pump characteristic (
HE
only)
bA
,
bb
,
C
(see p. 16)
–
Speed control (
R1
,
R2
only)
on
,
oFF
2)
oFF
Minimum speed (
AC
only)
30%
100%
50%
Minimum speed (
HE
+
bA
only)
0%
100%
25%
Minimum speed (
HE
+
bb
only)
0%
100%
75%
Sensor input for storage tank
temperature
1 ... 5
–
Sensor input for solid fuel boiler
temperature
1 ... 5
–
Switch-on temperature difference
T
diff on
T
diff off
+ 4 F
40 F
12 F
Switch-off temperature difference
T
diff off
0 F
T
diff on
– 4 F
6 F
Max. storage tank temperature
32 °F
300 °F
140 °F