10.3.6 Heat quantity
B
Calculates the acquired heat volume based on the following information:
• Supply temperature
• Return temperature
• Flow rate determined using the following methods:
– Calculated via pump speed
– Measured using a pulse water meter (terminal
5
)
Notes
– Calculation based on the pump speed cannot be performed
when
No system
(system
0
.
1
) has been selected.
– In drainback systems, the correct flow rate value can only be
read when the system is filled.
• Glycol proportion and accounting for the temperature dependent
thermophysical properties of the heat transfer fluid
Additional possibility: display of the amount of CO
2
saved by using the
system. The amount of CO
2
is calculated from the acquired heat volume.
To do this, the controller requires the conversion factor lbs
CO2
/kWh
therm
to be entered.
Display
Characteristic
min.
max.
Factory
setting
Activation
on
,
oFF
oFF
Type of flow rate acquisition
tyP
1
,
tyP
2
1)
–
l
g
Type 1: flow rate value at max.
speed F
max.
(pump 1).
When the Fig. at the left is dis-
played (value flashes), then enter
the value read from the flow rate
display.
F
min.
999.9
gal/min
0.0 gal/min
l
g
Type 1: flow rate value at min.
speed F
min.
(pump 1).
When the Fig. at the left is dis-
played (value flashes), then enter
the value read from the flow rate
display.
0.0 gal/min
F
max.
0.0 gal/min
Type 1: flow rate value at max.
speed F
max.
(pump 2)
2)
F
min.
999.9
gal/min
0.0 gal/min
Type 1: flow rate value at min.
speed F
min.
(pump 2)
2)
0.0 gal/min
F
max.
0.0 gal/min
l
g
Type 2: flow rate of the pulse
water meter in litres/pulse; see
the pulse water meter data
sheet.
1.0 gal...10.0 gal
,
1
l
,
10
l
,
25
l
–
gal
(no flow
rate value
selected)
Glycol proportion
0%
60%
40%
Supply sensor input (warm)
1 ... 5
–
Return sensor input (cold)
1 ... 5
–