Display
Characteristic
min.
max.
Factory
setting
Activation
on
,
oFF
oFF
Filling time
1 ... 10 minutes
3 minutes
Stabilising time
1 ... 15 minutes
2 minutes
Draining time:
1 ... 30 minutes
5 minutes
Short startup time
0 ... 60 seconds
0 seconds
Booster pump
on
,
oFF
oFF
Output (booster pump)
free output
R1
/
R2
/
R
S
–
Pump type (
R1
,
R2
only)
AC
,
HE
1)
AC
Pump characteristic (
HE
only)
bA
,
bb
,
C
(see p. 16)
–
1)
Notice
Standard pump: Set
AC
!
High-efficiency pump: Set
HE
!
External relay: Set
AC
pump type!
10.3.2 Circulation
Switches a circulation pump on and off on a temperature and/or time
controlled basis.
Temperature control: If the temperature in the circulation return falls
below the T
on
value, then the circulation pump is switched on until the
T
off
temperature is reached.
Time control: The circulation pump is switched on when the current
time lies within one of 3 configurable time windows.
Temperature and time control: The circulation pump is switched on when
the switch-on conditions for the temperature and time control are satisfied.
Note
Install the circulation sensor at least 1.5 m (60 inch) away from the storage
tank to avoid false measurements due to heat conduction of the pipes.