52
738.977 | 1149
EN
11
Technical data
11.1 StecaGrid Control I1
Input side 230 V AC
AC connection (Wieland Electric GST 18i3V
1P1)
1)
Data
Steca data connection
1)
Output side 230 V AC
AC contact plug (Wieland Electric GST 18i3V);
Mating plug included in delivery.
Main switch
Yes
Display
Yes
Dimensions (H x D x W)
250 x 175 x 70 mm
Weight
1.75 kg
Own consumption
2.7 W
Safety
Residual current monitor-
ing
The plant
must
be equipped with an AC/DC sen-
sitive residual current protection switch type B
in accordance with DIN VDE 0100-410.
Standards and certification marks
EMC: Emission EN 50081-1 (EN 55014 and EN 55022)
Interference immunity EN 50082-1
Safety EN 60950
Self-test As per DK5940
Degree of protection IP 20
Grid monitoring Direct component monitoring as per DK5940
Certification mark CE mark
1)
Both connection plugs are supplied with the inverter.
2)
DC sensitivity suitable for StecaGrid 300/500.
11.2 StecaGrid Remote
Display
of StecaGrid Control I1
Transceiver
868 MHz ISM
Power supply
2x LR06 (AA)
Range
approx. 100 m indoors
approx. 300 m outdoors
Dimensions (H x D x W)
140 x 103 x 35 mm
Weight
0.23 kg
Standards and certification marks
HF transmission EN 300 220
Degree of protection IP 20
11.3 AC cables and line circuit breakers
AC cable conductor cross-section
Line circuit breaker
1,5 mm
2
B16
2,5 mm
2
B16 or B25
Содержание StecaGrid Control I1
Страница 90: ...90 738 977 1149 Zertifikate Certificates Certificati...